Electrical supply
Warning
CAUTION
Caution
10
Plug the room unit into a power socket.
•
As standard the ACT 7 requires a fused electrical supply (UK 13A, Europe 16A) rated at
230 Volts, ~1N, 50Hz. The ACT 7 is equipped with a UK plug (CEE 7/7) as standard.
If an extension cable is used the following specifications must be complied to.
Extension cable
Extension cable
(length)
(min . width)
max. 10 m
2,5mm
10 m and more
4,0mm
Improper use of cables or using insufficient cable type can cause short circuit and fire
hazard
•
If the supply cord is damaged, it must be replaced by the manufacturer, its service agent
or similarly qualified persons in order to avoid a hazard.
•
Use extension cable with the right specification (be aware that most domestic propri-
etary extension cables are 1,5mm
•
If the cable is on a 'cable drum' then ensure that it is completely unwound in accordance
with the manufacturer's instructions
2
2
- this is not sufficient)
2
Installation: Handling and set-up