RESET-Mode:
In order to perform a RESET, proceed as follows:
1. Remove the batteries.
2. Press and hold the TEST button while reinserting the batteries. Pay attention to the correct polarity!
3. The LED lights solid red for about 3 seconds after inserting the batteries. Note: Keep and hold the TEST
button pressed!
4. When the LED light turns off, release the TEST button.
5. The LED light turns on. Press the TEST button again.The RESET process is completed by a short beep
sound.
Explanation of the LED modes :
LED flashes every 32 seconds:
LED flashes every second and alarm sounds:
Peep 0,5s –Pause 0,5s - Peep 0,5s – Pause 0,5s
- Peep 0,5s – Pause 1,5s LED flashes – repetition
of the signal:
Alarm sounds 2 x in quick succession and
after one second LED flashes (recurring
signal): Peep – Peep – Pause 1,2s – LED
flashes – repetition of the signal:
LED flashes every 8 seconds:
LED flashes every 32 seconds and a short
alarm tone sounds:
Every 32 seconds a short alarm tone sounds
and LED doesn´t flash:
Installation (Fig.7) :
1: Dowel
2. Mounting base
3. Holes for screws for fixing
4: Screw
5: Retainer of the bayonet connection
Attention:
Before drilling the mounting holes, make sure that there are no gas, electricity or water pipes at the
drilling location that could be damaged by this!
Attention
: The device is only ready for operation if the case is properly attached to the mounting base. Otherwise
the battery is deactivated and the device is not ready for use.
Install the heat detector in the middle of the room if possible. Observe a minimum distance of 0.5m from the side wall
and 0.6m from the corner of the room, as well as a maximum installation height of 6m (see Fig.6).
Remove the mounting plate located on the back of the housing by turning it counterclockwise.
Select an easily accessible installation location, as the heat detector must be checked weekly for proper
functioning!
Hold the mounting base to the position on the ceiling where you want to attach the unit. Then draw the holes
for the drill holes on the ceiling with a pencil.
This device is working properly..
TEST button is pressed or the alarm has been triggered by
heat. (Local alarm signal)
TEST button is pressed or the alarm has been triggered by
heat. (Radio alarm signal)
The unit is in the silent mode
Batteries are low. Replace the batteries!
The unit is defective or the maximum service life has been
reached. Replace the unit