Summary of Contents for Atest Gaz Alpa EcoWent XT

  • Page 1 User Manual Gas Detector Alpa EcoWent XT Product code: PW-097-CO POD-042-ENG R04...
  • Page 2 Systems for Monitoring, Detection and Reduction of gas hazards We invite you to familiarize yourself with our offer on www.atestgaz.pl We invite you to familiarize yourself with our offer on www.atestgaz.pl Atest Gaz A. M. Pachole sp. j. ul. Spokojna 3, 44-109 Gliwice Poland tel.: +48 32 238 87 94...
  • Page 3 www.atestgaz.pl Remarks and reservations Connection and operation of the device is allowed only after reading and understanding the contents of this document. Keep User Manual with the device for future use. The manufacturer bears no responsibility for errors, damages and failures caused by improper selection of devices and cables, improper installation or failure to understand the contents of this document.
  • Page 4: Table Of Contents

    Figure 8: Settings of the configuration switch......................14 Figure 9: Independent work and cooperation Alpa EcoDet XT..................14 Figure 10: Example connection of cables to the device.................... 18 Figure 11: Connection of the Alpa EcoWent XT Gas Detector into the star system............18 p. 4|24 User Manual: POD-042-ENG R04...
  • Page 5: Preliminary Information

    In addition, if it works in an alarm loop system (see Section 6.2, 6.3), at its input (via an XT T- connector) a current signal can be passed from the next detector – Alpa EcoWent XT or Alpa EcoDet XT.
  • Page 6: Table 1: Priorities Of The Alpa Ecowent Xt Gas Detector

    The Alpa EcoWent XT Gas Detector can work directly with the Alpa EcoDet XT (connection via X2 terminals). Then we get a couple of sensors that allows for the simultaneous detection of carbon monoxide (CO) and LPG (C Priorities...
  • Page 7: Safety

    www.atestgaz.pl possibly frequent readout, preferably daily, systematic ordering of inspections (see Subsection 9.4.3). 1.2.2 Warning 1 (threshold 1) / Warning 2 (threshold 2) It is a condition that occurs when a low gas concentration is detected that requires informing the user. Actions to be taken: check the cause, which can be e.g.: •...
  • Page 8 www.atestgaz.pl Do not install a gas detector in places exposed to direct sunlight and water. In the case of damage, shut down the detector, secure the connection cables, and conduct the service. All activities related to connecting detectors, signallers and other system components must be carried out while Control Unit's power supply is off.
  • Page 9: Description Of The Construction

    www.atestgaz.pl Description of the construction Configuration switch Electrical connections Mounting holes Sensor plate TEST buttom Gas inlet Optical controls Figure 2: The construction of the device and its dimensions Input-output interfaces Electric interfaces The appearance of the terminal strip is shown in Figure 2. Name Terminal Description...
  • Page 10: User Interface

    Detectors can be connected in two ways: star system (traditional) or, into a serial "bus" arrangement (alarm loop) – open or closed. Systems can be built of single Alpa EcoWent XT detectors or pairs (Alpa EcoWent XT along with the Alpa EcoWent XT detector). p. 10|24...
  • Page 11: Star System

    Figure 5: Connection with the Alpa MOD LED1 control unit into an open bus system In the last Alpa EcoWent XT detector (the most remote one from the control unit) of the open bus system, the configuration switch on the plate must be set to position 2 (see Figure 8).
  • Page 12: Closed Alarm Loop

    www.atestgaz.pl Closed alarm loop This system is different from the previous one in terms of connection of the end of the supply and signal line back to the control unit of the loop equipped with a test output (e.g. Alpa MOD LED1 Control Unit). In this way, it is possible to improve the power supply conditions of the sensor and resistance to damage.
  • Page 13: Device Configuration

    www.atestgaz.pl Number of detectors: 3 Number of detectors: 3 Bus 1 – Alarm zone 1 Bus 1 – Alarm zone 2 Figure 7: Connecting into two open bus systems servicing two zones Device configuration Detector location For correct operation of the system, it is necessary to configure the detectors by appropriately setting the configuration switch located in the detector (see Figure 2, 8).
  • Page 14: Independent Work And Cooperation With The Alpa Ecodet Xt Detector

    Jumper mounted for detector Alpa EcoWent XT working alone Alpa EcoWent XT cooperating with Alpa EcoDet XT Figure 9: Independent work and cooperation Alpa EcoDet XT In the case of working alone, it is necessary to pay attention to the need to mount the jumper in the terminal block X2.
  • Page 15: Diagnostics Of Electrical Connections - Searching For Connection Errors

    www.atestgaz.pl Diagnostics of electrical connections – searching for connection errors In the case when the detector signals problems with connections (see Section 5) the reasons of failure should be sought using the guidance contained in the Table 5. Indicator Additional conditions Possible cause of the problem detector works...
  • Page 16: Life Cycle

    YTKSY, OMY, LiYY type (bus). For connecting the Alpa EcoWent XT detector, it is necessary to apply a four-wire conductor. The selection of a specific cable type depends on the designer and should take into account the conditions in the place in which the gas detection system operates.
  • Page 17 www.atestgaz.pl When selecting the cable, it is necessary to pay attention to voltage drops on the lines. The power line should be designed in such a way that, at the lowest expected voltage of the line power supply, the voltage "seen" on the detector terminals does not drop below the permissible value (see Section 10).
  • Page 18: Figure 10: Example Connection Of Cables To The Device

    Control Unit Unused terminal S2 Figure 11: Connection of the Alpa EcoWent XT Gas Detector into the star system Only the S1 terminal is used. The configuration switch is always set in position 2 (last detector). For details, see Section 7.
  • Page 19 www.atestgaz.pl Install and provide power to the control unit. After the power supply is switched on, the state of "FAILURE" should be shown due to the lack of connected detectors. Turn off power to the control unit. Mechanically fastened detectors on the object. Connect the output of the first detector to the cable going into the control unit.
  • Page 20: Start-Up

    www.atestgaz.pl In the detectors, set the configuration switch in position 1. In the last detector, set the configuration switch in position 2 (see Figure 8). The control unit should show the state of OPERATION for the whole bus. Perform the test of the entire assembled bus. For this purpose, force the alarm on the last detector by pressing the TEST button in the detector.
  • Page 21: Periodical Operations

    9.4.1 Calibration During the operation of the system with Alpa EcoWent XT gas detectors, it is necessary to conduct periodic, systematic inspections of operation. The gas detector applied in the device is an element vulnerable to aging and environmental impacts, the natural effect of which is the decrease in its sensibility.
  • Page 22 www.atestgaz.pl The costs of calibration and travel should be incurred by the user. It is prohibited to test the sensor individually by applying a small amount of gas with an unknown composition and concentration on it, e.g. from a lighter. Such an operation leads to the poisoning of the sensor and the detector de-calibration.
  • Page 23: Utilization

    www.atestgaz.pl Utilization This symbol on a product or on its packaging indicates that the product must not be disposed of with other household waste. Instead, it is the user's responsibility to ensure disposal of waste equipment by handing it over to a designated collection point for the recycling of waste electrical and electronic equipment.
  • Page 24: List Of Consumables

    [2] PU-Z-032-ENG – Parameters of gas detectors with electrochemical sensor [3] PU-Z-099-ENG – Connection diagrams of gas detectors XT series [4] PU-Z-098-ENG – Maximum quantity of Alpa EcoWent XT and Alpa EcoDet XT detectors by cable type [5] PU-Z-039-ENG – Classification of chemicals used at Atest Gaz p.
  • Page 25 EU Declaration of Conformity Atest Gaz A. M. Pachole sp. j. declares with full responsibility, that the product: (Product description) (Trade name) (Type identifier or Product code) Gas Detector Alpa EcoWent XT PW-097 complies with the following Directives and Standards: in relation to Directive 2014/30/EU –...
  • Page 26 www.atestgaz.pl Parameters of gas detectors with electrochemical sensor Detected substances Detectors equipped with electrochemical sensors are used for measuring and detecting the presence of specific substances in gaseous atmospheres in concentrations generally above single "ppm," but in some cases (e.g. oxygen, hydrogen), the concentration may be tens or hundreds of thousands "ppm". These gases have characteristic measurement ranges.
  • Page 27 www.atestgaz.pl the measured gas. Owing to electrode reactions, electrons are generated, whose orderly flow – electric current, is proportional to the concentration of the detected gas. 1 – inlet of sensor 2 – measuring electrode 3 – extra electrode 4 – electrolyte 5 –...
  • Page 28 www.atestgaz.pl Ingredient C [% vol] C [ppm] Nitrogen 78.084 780 840 Oxygen 20.946 209 460 Argon 0.934 9 340 Carbon dioxide 0.0360 Neon 0.00181 18.18 Helium 0.00052 5.24 Methane 0.00017 1.70 Krypton 0.00011 1.14 Hydrogen 0.00005 0.50 Xenon 0.000008 0.087 Table 2: Typical composition of atmospheric air When gas concentrations in the atmosphere differ significantly from those indicated in the table 2, it is necessary to conduct the analysis of the impact of such a situation on the detector operation.
  • Page 29 www.atestgaz.pl with electrochemical sensors are designed to measure and detect the short-term presence of certain gases in the atmosphere. Both the more sustained concentration with values falling within the range of measurement, and even instantaneous concentrations outside the measuring range lead to a rapid wear of the sensor.
  • Page 30 Connection diagrams of gas detectors XT series Examples of connection between Alpa EcoWent XT and Alpa EcoDet XT gas detectors with control units are shown in the drawings. Control Unit Input Input T-connector XT T-connector XT T-connector XT Jumper...
  • Page 31 While connecting detectors to the control loop pay attention to the position of an internal configuration switch (the last detector in the loop or a transient detector). Atest Gaz A. M. Pachole sp. j. tel.: +48 32 238 87 94 p.
  • Page 32 T-connector XT T-connector XT T-connector XT Figure 3: Connection Alpa EcoWent XT and Alpa EcoDet XT Gas Detectors with control unit into an open bus system Please make sure that configuration jumpers are in correct positions. The jumper in the terminal block X2 of the Alpa EcoWent XT must be installed when the detector is not directly coupled with the Alpa EcoDet XT detector).
  • Page 33 T-connector XT T-connector XT T-connector XT Figure 4: Connection Alpa EcoWent XT and Alpa EcoDet XT Gas Detectors with control unit into an closed bus system Please make sure that configuration jumpers are in correct positions. The jumper in the terminal block X2 of the Alpa EcoWent XT must be installed when the detector is not directly coupled with the Alpa EcoDet XT detector).
  • Page 34 Control Unit Figure 5: Connection Alpa EcoWent XT and Alpa EcoDet XT Gas Detectors with control unit into a star- shaped system Please make sure that configuration jumpers are in correct positions. The jumper in the terminal block X2 of the Alpa EcoWent XT must be installed when the detector is not directly coupled with the Alpa EcoDet XT detector).
  • Page 35 1393 1196 1396 1200 1400 1204 Table 1: Maximum quantity of Alpa EcoWent XT detectors – open loop configuration Atest Gaz A. M. Pachole sp. j. tel.: +48 32 238 87 94 p. 1/7 Appendix: PU-Z-098-ENG R06 ul. Spokojna 3, 44-109 Gliwice, Poland fax: +48 32 234 92 71 VAT No.: PL 9691433231...
  • Page 36 Length L2 [m] Length L1 [m] Detectors installed 30 m apart Figure 2: Open loop configuration for Alpa EcoDet XT detectors Cross-section of Alpa EcoWent XT Gas Detector a single cable System without backup battery supply System with backup battery supply conductor...
  • Page 37 L1 [m] L2 [m] Quantity of sets 0,75 Table 3: Maximum quantity of sets of Alpa EcoWent XT and Alpa EcoDet XT – open loop configuration Atest Gaz A. M. Pachole sp. j. tel.: +48 32 238 87 94 p. 3/7 Appendix: PU-Z-098-ENG R06 ul.
  • Page 38 1880 1619 1882 1622 1884 1625 Table 4: Maximum quantity Alpa EcoWent XT – closed loop configuration Atest Gaz A. M. Pachole sp. j. tel.: +48 32 238 87 94 p. 4/7 Appendix: PU-Z-098-ENG R06 ul. Spokojna 3, 44-109 Gliwice, Poland fax: +48 32 234 92 71 VAT No.: PL 9691433231...
  • Page 39 L1 [m] L2 [m] Quantity of detectors 0,75 Table 5: Maximum quantity of Alpa EcoDet XT – closed loop configuration Atest Gaz A. M. Pachole sp. j. tel.: +48 32 238 87 94 p. 5/7 Appendix: PU-Z-098-ENG R06 ul. Spokojna 3, 44-109 Gliwice, Poland fax: +48 32 234 92 71 VAT No.: PL 9691433231...
  • Page 40 L1 [m] L2 [m] Quantity of sets 0,75 Table 6: Maximum quantity of sets of Alpa EcoWent XT and Alpa EcoDet XT – closed loop configuration Atest Gaz A. M. Pachole sp. j. tel.: +48 32 238 87 94 p. 6/7 Appendix: PU-Z-098-ENG R06 ul.
  • Page 41 Cross-section of a System with backup battery supply (U = 20 V) IN(min) single cable One Alpa EcoWent XT Gas Detector One Alpa EcoDet XT Gas Detector conductor at the end of the line at the end of the line...
  • Page 42 www.atestgaz.pl Classification of chemicals used at Atest-Gaz Because of the need to present a consistent and high level of maintenance services, to ensure the safety of the calibration process and to create a basis for a rational calculation of the costs of this process, Atest-Gaz developed the "Classification of Chemical Substances"...
  • Page 43 www.atestgaz.pl Category Description Terms of facility calibration No precipitations, no strong winds, Cylinder gases, temperature over – 10 C¹. stable environment In other cases, calibration at a location that meets the above conditions (necessary to remove the detectors). No precipitations, no strong winds, Cylinder gases, temperature over + 10...