4. CROSS-CONNECT JUMPER ROUTING RULES

A. Cross-Connect Cabling
4.01 Cross-connect jumpers should be routed as
shown in
Figure
2. Whenever a cross-connect changes
direction, it should do so at a point where a ring, tray
or fanning strip is placed. This allows the cross con-
nect to be dressed neatly without strain or interference
with any other portion of the bays.
4.02 All cross connect jumpers should use the hori-
zontal cable ways between bays, and vertical cable
ways within bays. To prevent unnecessary jumper
buildup and congestion, all discontinued cross con-
nects should be removed from the DSX cable ways.
Jumpers should be sized to the proper length, including
a maximum of 3 inches of slack at each end.
BAY 1
BAY 2
ORIZONTAL
JUMPER
WIREWAYS
CROSS-
D
CONNECT
E
JUMPER
A
VERTICAL
JUMPER
C
WIREWAYS
B
ORIZONTAL
D
JUMPER
WIREWAYS
ROUTING RULES
A.
All jumpers in the left-hand side of the cross-connect field should enter and
leave the bay from the left vertical wireways.
B.
All jumpers in the right-hand side of the cross-connect field should enter
and leave the bay from the right vertical wireways.
C.
All intrabay cross-connects should use the vertical rings except when
terminations are in the same panel.
D.
All interbay cross-connects should use the horizontal wireways.
E.
All jumpers originating in the upper half of the cross-connect field should
route via the upper horizontal wireways.
F.
All jumpers originating in the lower half of the cross-connect field should
route via the lower horizontal wireways.
Figure 2. Jumper Routing Rules
© 1995, ADC Telecommunications, Inc.
ADCP-80-348
Issue 1, May 1995