When a test run is not
performed properly
• When a test run is not performed properly, refer
to the error code and the part to be checked on
"Troubleshooting".
• When a test run is executed before installing
the external duct, a protection control may be
activated and lets the unit stop and the code
P12 may be displayed. (This is not due to a
malfunction but to the current control function of
the DC motor in this unit.)
When a test run executed before installing the
external duct, select "Low" for the fan speed
level or cover the air discharge.
• In addition, stop the operation before replacing
the High-effciency filter or opening the service
panel.
After the test run, reset the circuit breaker of the
indoor unit.
Monitoring function
This function can be used to call the service
monitor mode from the remote controller during a
test run to obtain the temperature of the sensors
of the remote controller, indoor unit, and outdoor
unit.
1
1, 2
Indoor unit
number
4
Data
1
Push and hold menu button for 10 seconds or
more. "Monitoring function" is displayed on a
screen.
2
Every pushing [
unit numbers in group control are displayed
successively.
3
Push OFF timer button to confirm the selected
indoor unit.
4
Every pushing [
the item is changed successively.
5
After you have finished checking, push
"ON/OFF" button, return to normal mode.
‒ 42 ‒
Installation Manual
3
2, 4
5
"Monitoring function" display
] [
] buttons, the indoor
] [
] buttons, Code No. of
42-EN