Toshiba RAV-HM561KRTP-E Installation Manual page 42

Hide thumbs Also See for RAV-HM561KRTP-E:
Table of Contents

Advertisement

4
After the test run, push OFF timer button to
stop a test run.
([TEST] disappears on the display and the air
conditioner enters the normal stop mode.)
Wireless remote controller
1
Turn on the power of the air conditioner.
When power is turned on for the first time
after installation, it takes approx. 5 minutes
until the remote controller becomes
available. In the case of subsequent
power-on, it takes approx. 1 minute until
the remote controller becomes available.
Execute a test run after the predetermined
time has passed.
2
Push "ON/OFF" button on the remote
controller, select [
with "MODE" button, and then select
[
HIGH] with "FAN" button.
3
Cooling test run
Set the temperature to 17°C
with the temp. setup buttons.
4
Cooling test run
After confirming a signal
receiving sound "beep"
immediately set the
temperature to 18°C with the
temp. setup buttons.
5
Cooling test run
After confirming a signal
receiving sound "beep"
immediately set the
temperature to 17°C with the
temp. setup buttons.
41-EN
Cool] or [
Heat]
Heating test run
Set the temperature to 30°C
with the temp. setup buttons.
Heating test run
After confirming a signal
receiving sound "beep"
immediately set the
temperature to 29°C with the
temp. setup buttons.
Heating test run
After confirming a signal
receiving sound "beep"
immediately set the
temperature to 30°C with the
temp. setup buttons.
6
Repeat procedures
Indicators "Operation" (green), "Timer"
(green), and "Ready" (orange) in the
wireless receiver section flash in approx.
10 seconds, and the air conditioner starts
operation. If any of these indicators does
not flash, repeat procedures
7
Upon completion of the test run, push
"ON/OFF" button to stop operation.
<Overview of test run operations using the
wireless remote controller>
Cooling test run:
ON/OFF → 17°C → 18°C → 17°C → 18°C →
17°C→ 18°C → 17°C → (test run) → ON/OFF
Heating test run:
ON/OFF → 30°C → 29°C → 30°C → 29°C →
30°C→ 29°C → 30°C → (test run) → ON/OFF
Wired remote controller
1
When TEMPORARY button is pushed for
10 seconds or more, "Pi!" sound is heard
and the operation changes to test run.
After approx. 3 minutes, a cooling
operation starts forcedly.
Check cool air starts blowing. If the operation
does not start, check wiring again.
2
To stop a test operation, push TEMPORARY
button once again (Approx. 1 second).
Check wiring / piping of the indoor and outdoor
units in test run.