Toshiba RAV-HM561KRTP-E Installation Manual page 33

Hide thumbs Also See for RAV-HM561KRTP-E:
Table of Contents

Advertisement

Remote controller sensor
The temperature sensor of the indoor unit
senses room temperature usually. Set the remote
controller sensor to sense the temperature around
the remote controller.
Select items following the basic operation
1
2
3
procedure (
[32]
• Specify
for the Code No. in Procedure
• Select the following data for the set data in
5
Procedure
.
Set data
Remote controller sensor
0000
Not in use (Factory default)
0001
When
flashes, the remote controller sensor is
defective.
Select the set data [0000] (not in use) or replace
the remote controller.
Communication type
When connecting to the central control device
dedicated to TCC-Link, it is necessary to change
to TCC-Link.
Follow to the basic opreration procedure
1
2
3
4
5
(
[FC]
• Specify
for the Code No. in Procedure
• Select the set data [0000] (TCC-Link) in
5
Procedure
.
Set data
Communication type
0000
0004
TU2C-Link (Factory default)
Fan speed setting when
thermostat-OFF in cooling mode
Set the fan speed when the room temperature
reaches the set temperature in the cooling mode.
Follow to the basic opreration procedure
1
2
3
4
5
(
[9A]
• Specify
for the Code No. in Procedure
• Select the following data for the set data in
5
Procedure
.
Fan speed when thermostat-OFF
Set data
0000
Remote controller setting
Extremely low speed (UL)
0001
4
5
6
7
).
In use
6
7
).
TCC-Link
6
7
).
in cooling mode
(Factory default)
8°C operation
Pre-heating operation can be set for cold regions
where room temperature drops to below zero.
Follow to the basic opreration procedure
1
2
3
(
[d1]
• Specify
• Select the following data for the set data in
4
.
5
Procedure
Set data
0000
0001
Installing optional parts
When installing optional parts, data setup may be
required with remote controller.
Be sure to set the data, according to Installation
Manual for optional parts.
Information
The following functions require a connection
with the RBC-AMTU
remote controller. For details, refer to the manual
included with the remote controller.
• Individual unit selection during group operation
4
.
• Individual setting of louver position (wind
direction)
• Swing type setting
• Louver lock (no swing) setting
• Energy saving operation (Power saving
operation)
• Notification of filter cleaning time
Others
The following functions can be used with this
model.
Refer to the Service Manual for more information.
• Rotation / backup operation
• Free cooling
• Secondary heating
4
• Power shift
.
‒ 32 ‒
Installation Manual
4
5
6
7
).
for the Code No. in Procedure
.
8°C Operation setting
None (Factory default)
8°C Operation setting
and RBC-AMSU
4
.
32-EN

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rav-hm801krtp-eRav-hm901krtp-e