Functioning Anomalies - Immergas VICTRIX 26 2 I Manual

Condensation-type wall-hung boiler
Hide thumbs Also See for VICTRIX 26 2 I:
Table of Contents

Advertisement

Technical Documentation

Functioning anomalies.

ERROR 01
230 VAC are present on clamps 2-3 of connector X7.
230 VAC are present at the ends of the igniter.
01
The cables between igniter and electrodes corresponds.
a
The igniter makes the spark.
Check the correct positioning and the correct distance of the ignition electrodes (see air-gas circuit) and replace them if necessary.
230 VAC are present on clamps 6-7 of connector X7.
N.B: measure the voltage within the safety time (8-10 s).
The connector and relative wiring between gas valve and P.C.B.
are OK.
01
b
The position and the distance of the ignition electrodes with respect
to the burner is OK (see air-gas circuit).
Replace the gas valve.
N.B.: before replacing the valve make sure that there is enough gas inlet dynamic pressure and that the gas valve is correctly calibrated.
The electrode detects a direct current of 6-8 µA during the burner
ignition phase.
01
c
There are no combustion products in the air intake pipe.
N.B.: check the absence of CO
intake pipe.
Replace the P.C.B.
ERROR 02
The wiring between safety thermostat, flue safety thermofuse,
exchanger safety thermofuse and P.C.B. is OK.
The flue safety thermofuse positioned to protect the flue extraction
elements is OK.
02
a
The exchanger safety thermofuse positioned to protect the conden-
sation module is OK.
The safety thermostat functions regularly (intervention temperature
higher than 100°C).
Replace the P.C.B.
STV2I ed 11/09
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
or other combustion products in the
2
Yes
Yes
Yes
Yes
Yes
No ignition block
Replace the P.C.B.
No
Replace wiring.
No
Restore the electric connection/replace the wiring.
No
Replace the igniter.
No
No
Replace the P.C.B.
No
Restore the electric connection/replace the wiring.
No
Restore the position and distance of the ignition electrodes.
Replace the detection electrode and/or relative wiring.
Check correct position and distance between electrode and burner.
No
Check that siphon and the condensate exhaust duct are not blocked.
Check the correct positioning of the terminals, of all joints and
gaskets, to prevent the recirculation of the combustion products inside
No
the pipes.
N.B.: the error 01 could appear after the visualizing of the error 38.
Over-heating safety thermostat block
Restore the electric connection/replace the wiring.
No
Replace the thermofuse positioned on the flue hood. N.B.: The cause
of breakage (opening) of the fuse must be identified before switching
No
the boiler back on.
Replace condensation module. N.B.: The cause of breakage (opening) of
No
the fuse must be identified before switching the boiler back on.
Replace the over-heating safety thermostat.
No
56
Technical Documentation
VICTRIX 2 I Export