Channel
Diagnosis
Error
Alarm Type
Type
Channel Diagnosis
265
Appears/Disappears
Channel Diagnosis
266
Appears/Disappears
Channel Diagnosis
267
Appears/Disappears
Channel Diagnosis
268
Appears/Disappears
Channel Diagnosis
269
Appears/Disappears
Channel Diagnosis
270
Appears/Disappears
Channel Diagnosis
271
Appears/Disappears
Channel Diagnosis
272
Appears/Disappears
Channel Diagnosis
273
Appears/Disappears
Channel Diagnosis
274
Appears/Disappears
Diagnostics
Module or
Channel
Cause
Error
Channel
Scaling fault
Channel
Upper clamp fault
Channel
Lower clamp fault
Channel
Non-volatile store fault
Thermistor fault
The thermistor in the
Channel
thermocouple carrier
is out of range
Automatically restart
Channel
after a fatal error
occurred
Loss of power input 1
Module
fault
Loss of power input 2
Module
fault
Loss of terminal block
Module
fault
The module internal
Module
temperature exceeds
the allowable limit.
Fault Text
Recommended Action
There are no corrective
Scaling Error
actions for this. Try
replacing the I/O module.
Bring process value below
Upper Clamp
configured upper clamp
Limit
limit level.
Bring process value above
Lower Clamp
configured lower clamp
Limit
limit level.
There are no corrective
Error writing to
actions for this.
non-volatile
Try store again or fix
memory
hardware.
Verify the thermocouple
Thermistor fault
carrier.
There are no corrective
actions for this.
Restart after fatal
Successfully restarting
error.
RX3i CEP module again
may eliminate the fault.
Verify field power to the
power input 1 is wired and
energized. If there did
Loss of RX3i CEP
expect no power, set
power input 1
power supply
configuration to Single in
configuration tool.
Verify field power to the
power input 1 is wired and
energized. If there did
Loss of RX3i CEP
expect no power, set
power input 2
power supply
configuration to Single in
configuration tool.
Verify the terminal block is
Loss of terminal
installed on specified
block
module.
Over
Decrease the temperature.
temperature