4. USER INTERFACE (continued)

4.5 Water flow setting

While the heat pump is running and the water inlet and outlet valves are open,
adjust the by-pass valve to obtain a difference of 2°C between the water
inflow and outflow temperature (see functional diagram
You can check the setting by viewing the inflow and outflow temperatures
directly on the control panel by following the procedure below.
Inflow
temperature
5 s
Then adjust the by-pass to obtain a difference of 2°C between the inflow and
the outflow.
Press
once to exit the menu.
• Opening the bypass valve results in a lower flow in the heat pump's
exchanger, leading to an increase in the inflow/outflow temperature
difference.
• Closing the bypass valve results in a higher flow in the heat pump's
exchanger, leading to a decrease in the inflow/outflow temperature
difference.
You can check the setting by viewing the inflow/outflow
temperatures (1-2) directly in the "EyesPool Inverter
Connect" app (see
Outflow
temperature
).
§4.6
).
§3.1
10 s
1
2
15