3. INSTALLATION AND CONNECTION (continued)
The electrical power supply must have, when appropriate, a fuse
protection device like a feed motor (aM) or D curve circuit breaker as
well as a differential circuit breaker 30 mA (see following table).
Models
V/Ph/
Power supply
Hz
aM type fuse
A
calibre
Curve D
A
circuit breaker
Cable section
mm
Use an RO 2V/R 2V or equivalent power cord.
The cables sections are given for a maximum length of 25 m. They
must however be checked and adjusted according to the installation
conditions.
Always shut down the main power supply before opening the electrical
control box.

3.5 Initial start-up

Start-up procedure – once installed, perform the following steps:
1) Turn the fan by hand to check that it turns freely, and that the blades are
properly attached to the motor shaft.
2) Check that the unit is correctly connected to the main power supply (see
wiring diagram in the appendix).
3) Check that all the water valves are open, and that the water flows towards
the unit before switching on the heating mode.
4) Turn on the filtration pump.
5) Check that the condensate drainage hose is attached correctly and does
not cause an obstruction.
6) Turn on the unit's power supply, then press the On/Off button
control panel.
10
HP3051DT3HM
230 V
1/50 Hz
6 aM
6 D
3G 1,5
2
HP3081DT3HM
HP3111DT3HM
230 V
1/50 Hz
10 aM
10 D
3G 2,5
HP3131DT3HM
230 V
230 V
1/50 Hz
1/50 Hz
16 aM
16 aM
16 D
16 D
3G 2,5
3G 2,5