3. INSTALLATION AND CONNECTION (continued)

3.6 Water flow setting

While the heat pump is running and the water inlet and outlet valves are open,
adjust the by-pass valve to obtain a difference of 2°C between the water inflow
and outflow temperature (see Functional Diagram Section 3.1). You can check
the setting by viewing the inflow (T02)/outflow (T03) temperatures directly on
the control panel by following the procedure below.
Then adjust the by-pass to obtain a difference of 2°C between T03 and T02
Press the MODE
Press
button for 10
until 022 is displayed
seconds
Press MODE to
validate
Press
Press MODE
until T02 is displayed
to display the water
inlet value
Press MODE again
to return to T02
Press MODE
Press
to display the water
until T03 is displayed
outlet value
Press
twice to exit the menu
Note: Opening the by-pass valve creates a weaker flow which results in an
Closing the by-pass valve creates a stronger flow which results in a
10