3.1 ST5 - supply voltage

The SI 010 CNV can be connected to either 230/115 VAC or
Caution
24 VDC. It must NOT be connected to both voltages.
In position ST5, SI 010 CNV can be set to either 230 V or 115 V supply
voltage:
one jumper across the two pins in the middle = 230 V
two jumpers as shown in fig. 4 = 115 V.
If the converter is connected to 24 VDC, the configuration of ST5 has no
function.
Set to 230 V (factory setting)
Fig. 4
How to set SI 010 CNV to 230 V and 115 V

3.2 ST3 and ST4 - sensor inputs

The sensors are available in two versions with different output signals, either
0.5 - 3.5 V or 0.5 - 4.5 V. The converter is compatible with both signal types
which are configured in short-circuit positions ST3 and ST4.
Short-circuit
position
ST3
ST4
Location
Function
(see fig. 7)
Input 1, input voltage 0.5 - 3.5 V
L
(factory setting)
H
Input 1, input voltage 0.5 - 4.5 V
Input 2, input voltage 0.5 - 3.5 V
L
(factory setting)
H
Input 2, input voltage 0.5 - 4.5 V
Set to 115 V