3.4 Configuration examples

Fig. 7
Configuration from factory
Figure 7 shows the factory configuration (jumpers are shown as light grey
rectangles): The supply voltage is set to 230 VAC (possibly 24 VDC), both
sensor inputs are set to 0.5 - 3.5 V, and both signal outputs to 4-20 mA.
1
115V
2
230V
3
115V
4
ST1: Ch1 out - I=4-20mA ; U1=1-5V; U2=2-10V
ST2: Ch2 out - I=4-20mA ; U1=1-5V; U2=2-10V
ST3: Ch1 input voltage span; L=0.5-3.5; H=0.5-4,5
ST4: Ch1 input voltage span; L=0.5-3.5; H=0.5-4,5
1
1
I
2
2
U1
3
3
U2
4
4
ST1 ST2
ST3
ST4
L H
H L