Adding Refrigerant - Bosch Climate 5000 Series Installation Instructions Manual

Multi zone ductless air conditioner / heat pump
Hide thumbs Also See for Climate 5000 Series:
Table of Contents

Advertisement

Installation Instructions

9.3 Adding Refrigerant

CAUTION: CONTAINS REFRIGERANT
Refrigerant charging must be performed after wiring,
vacuuming, and the leak testing.
DO NOT exceed the maximum allowable quantity of
refrigerant or overcharge the system. Doing so can damage
the unit or impact its functionality.
DO NOT exceed the maximum allowable refrigerant length.
Refer to table 4.
Charging with unsuitable substances may cause explosions
or accidents. Ensure that the appropriate refrigerant is used.
Refrigerant containers must be opened slowly. Always use
protective gear when charging the system.
DO NOT mix refrigerants types.
Depending on the length of connective piping or the pressure of the evacuated
system, you made need to add refrigerant. Refer to table below for refrigerant
amounts to be added:
Additional refrigerant per pipe length
Type
Model Name
BMS500-AAM018-1CSXRC
BMS500-AAM027-1CSXRC
Regular
System
BMS500-AAM036-1CSXRC
BMS500-AAM048-1CSXRC
BMS500-AAM018-1CSXHC
BMS500-AAM027-1CSXHC
Max
Performance
BMS500-AAM036-1CSXHC
BMS500-AAM048-1CSXHC
Table 12
* Calculated based on 9K IDU
2 2 |
Model #
Standard refrigerant pipe length (ft / m)*
8-733-956-199
49ft (15m)
8-733-956-200
74ft (22.5m)
8-733-956-201
98ft (30m)
8-733-956-226
123ft (37.5m)
8-733-956-202
49ft (15m)
8-733-956-203
74ft (22.5m)
8-733-956-227
98ft (30m)
8-733-956-204
123ft (37.5m)
Bosch Climate 5000 Series Multi Zone Ductless Air Conditioner / Heat Pump (06.2022)
Additional Refrigerant charge per ft
Refrigerant Type: R410A
For the Indoor unit with 1/4" liquid line diameter:
(actual pipe length – standard length) 0.16oz/ft (15g/m)
For the Indoor unit with 3/8" liquid line diameter:
(actual pipe length– standard length) 0.32oz/ft (30g/m)
Actual pipe length is measured based on the refrigerant
liquid line only.
See Section 9.4 Calculation Steps to determine the
additional refrigerant amount if the Indoor units have
diff erent liquid line diameters. (Refer to table 8 for
Indoor unit liquid line diameters)