Bosch Climate 5000 Series Installation Instructions Manual page 13

Multi zone ductless air conditioner / heat pump
Hide thumbs Also See for Climate 5000 Series:
Table of Contents

Advertisement

Connecting Multiple Capacity Indoor Units
When diff erent capacity units need to be connected, it is recommend to connect
the one has highest capacity at the bottom and the smallest unit at the top of the
ODU refrigerant connection manifold. For example, if the system has one 9K, 18K,
and 24K Indoor units, the 24K indoor unit should be connected via the port A. and
the 9K indoor unit should be connected via the port C. (See Fig. 11)
Refrigerant pipe diameter
Indoor unit capacity (Btu/h)
Liquid line O.D. (in / mm)
6K / 9K
1/4" / Φ6.35
12k / 18k
1/4" / Φ6.35
24K / 30K /36K
3/8" / Φ9.52
Table 8
Multi-zone condensing section refrigerant line connection sizes and maximum
indoor unit
Type
Model Name
BMS500-AAM018-1CSXRC
BMS500-AAM027-1CSXRC
Regular
System
BMS500-AAM036-1CSXRC
BMS500-AAM048-1CSXRC
BMS500-AAM018-1CSXHC
BMS500-AAM027-1CSXHC
Max
Performance
BMS500-AAM036-1CSXHC
BMS500-AAM048-1CSXHC
Table 9
Figure 11
Bosch Climate 5000 Series Multi Zone Ductless Air Conditioner / Heat Pump (06.2022)
Vapor line O.D. (in / mm)
3/8" / Φ9.52
1/2" / Φ12.7
5/8" / Φ15.9
Model #
Liquid Side inch (mm)
8-733-956-199
2 X 1/4" (Φ6.35mm)
8-733-956-200
3 X 1/4" (Φ6.35mm)
8-733-956-201
4 X 1/4" (Φ6.35mm)
8-733-956-226
5 X 1/4" (Φ6.35mm)
8-733-956-202
2 X 1/4" (Φ6.35mm)
8-733-956-203
3 X 1/4" (Φ6.35mm)
8-733-956-227
4 X 1/4" (Φ6.35mm)
8-733-956-204
5 X 1/4" (Φ6.35mm)
Gas Side inch (mm)
2 X 3/8" (Φ9.52mm)
3 X 3/8" (Φ9.52mm)
3 X 3/8" (Φ9.52mm) + 1 x 1/2" (Φ12.7mm)
3 X 3/8" (Φ9.52mm) + 2 x 1/2" (Φ12.7mm)
2 X 3/8" (Φ9.52mm)
3 X 3/8" (Φ9.52mm)
3 X 3/8" (Φ9.52mm) + 1 x 1/2" (Φ12.7mm)
3 X 3/8" (Φ9.52mm) + 2 x 1/2" (Φ12.7mm)
Installation Instructions
Maximum IDU
2
3
4
5
2
3
4
5
| 13