9.4 Calculation Steps

Step1: Calculate the "Estimated" refrigerant pre-charge amount.
Please note this value is only used to calculate the additional refrigerant
charge amount.
 Estimated Pre-charge Amount = Standard Refrigerant Pipe Length *
0.16oz/ft. (15g/m)
Step2: Calculate the required charge amount for each zone
(Refer to Table 8 for Indoor unit liquid line diameter)
 If the Zone 1 Indoor unit has 3/8inch liquid line diameter:
Zone 1 Charge Amount = Zone 1 Refrigerant Pipe Length * 0.32oz/ft (30g/m)
 If the Zone 2 Indoor unit has 1/4 inch liquid line diameter:
Zone 2 Charge Amount = Zone 2 Refrigerant Pipe Length * 0.16oz/ft.
(15g/m)
 Total zone charge amount = Zone 1 charge amount + Zone 2 charge
amount + Zone 3 charge amount + ... up to 5 zones.
Step3: Calculate the additional refrigerant needed
 Additional Refrigerant Amount = Total Zone Charge Amount - Estimated
Pre-charge Amount
For example:
One 36K ODU (BMS500-AAM036-1CSXHC) paired with below Indoor units.
One 9K wall mounted unit with 30ft refrigerant pipe
One 18K Cassette unit with 30ft refrigerant pipe.
One 24K wall mounted unit with 50ft refrigerant pipe.
1. Step1: Calculate the "Estimated" refrigerant charge. Please note this value
is only used to calculate the additional refrigerant charge amount.
Estimated Refrigerant Charge Amount = 98ft * 0.16oz/ft. = 15.68oz
2. Step2: Calculate the required charge amount for each zone. Refer to table 8
for Indoor unit liquid line size
Zone 1: 24K wall mounted Indoor unit
Zone 1 Charge Amount = 50ft * 0.32oz/ft. = 16oz
Zone 2: 18K Cassette Indoor unit
Zone 2 Charge Amount = 30ft * 0.16oz/ft. = 4.8oz
Zone 3: 9K wall mounted Indoor unit
Zone 3 Charge Amount = 30ft * 0.16oz/ft. = 4.8oz
Total Zone Charge Amount = 16oz + 4.8oz + 4.8oz = 25.6oz
3. Step3: Calculate the additional refrigerant needed
Additional Refrigerant Amount = 25.6oz – 15.68oz = 9.92oz
Bosch Climate 5000 Series Multi Zone Ductless Air Conditioner / Heat Pump (06.2022)