8.3 Adding Refrigerant
In North America, the standard pipe length is 7.5m (25ft). The minimum length
is 10ft. The factory charge is suitable for pipe lengths of 10 -25ft. If piping length
exceeds 25ft, the additional refrigerant to be charged can be calculated using the
formula in Table 8. For multi-zone units refer to the multi-zone installation and
operation manual.
Additional refrigerant per pipe length
Connective Pipe
< Standard pipe length
> Standard pipe length
Table 8
Single zone refrigerant pipe summary
Model - Single Zone
IDU
BMS500-AAU006-1AHWXC
BMS500-AAS009-1CSXRC
BMS500-AAS009-1CSXRC
BMS500-AAU009-1AHWXC
BMS500-AAS009-1CSXHC
BMS500-AAS012-1CSXRC
BMS500-AAU012-1AHWXC
BMS500-AAS012-1CSXHC
BMS500-AAS018-1CSXRC
BMS500-AAU018-1AHWXC
BMS500-AAS018-1CSXHC
BMS500-AAS024-1CSXRC
BMS500-AAU024-1AHWXC
BMS500-AAS024-1CSXRC
BMS500-AAS030-1AHWXC
BMS500-AAS030-1CSXRC
BMS500-AAS036-1AHWXC
BMS500-AAS036-1CSXRC
Table 9
CAUTION: CONTAINS REFRIGERANT
NEVER mix refrigerant types.
2 6 |
Liquid Side: Ø 6.35mm (ø 1/4")
Inverter R410A:
(Pipe length – standard length) x 15g/m
(Pipe length – standard length) x 0.16oZ/ft
Capacity (Btu/h)
ODU
6K
9K
12K
18K
24K
30K
36K
Bosch Climate 5000 Series Wall Mounted Ductless Split Air Conditioner / Heat Pump (06.2022)
Additional Refrigerant
N/A
(Pipe length – standard length) x 30g/m
(Pipe length – standard length) x 0.32oZ/ft
Inch O.D.
Max. Equivalent Length
Liquid Line
Vapor Line
1/4"
3/8"
1/4"
3/8"
1/4"
1/2"
1/4"
1/2"
3/8"
5/8"
3/8"
5/8"
3/8"
5/8"
Liquid Side: Ø 9.52mm (ø 3/8")
Inverter R410A:
Max. Height Variation
m(ft)
m(ft)
30 (98ft)
20 (66ft)
30 (98ft)
20 (66ft)
30 (98ft)
20 (66ft)
30 (98ft)
20 (66ft)
50 (164ft)
25 (82ft)
50 (164ft)
25 (82ft)
65 (213ft)
30 (98.5ft)