ABB DCS800 Firmware Manual page 12

Hide thumbs Also See for DCS800:
Table of Contents

Advertisement

12
Field heat On
When parameter FldHeatSel (21.18) = On, the feature works as follows:
Condition
Power Up:
Start drive:
Normal stop:
Off2 while running:
* Parameter Off2 Emergency Off / Coast Stop (10.08) must be set to a valid input bit number for
this to be valid. Default value is DI-4.
** If parameter 44.04 is set below 100%, field will be at this reduced level while motor is stopped.
Field heat OnRun
When FldHeatSel (21.18) = OnRun, the feature works as follows:
Run (StartStop,
Jog1, Jog2, etc.)
Off
On
On or Off
All other conditions
* Parameter Off2 Emergency Off / Coast Stop (10.08) must be set to a valid input bit number for
this to be valid. Default value is DI-4.
** If parameter 44.04 is set below 100%, field will be at this reduced level while motor is stopped.
The Estop Input
In both modes of operation, the estop input (configured with parameter 10.09) is cleared
while the drive is off, the field will turn off. It will not turn back on again until the estop input
is again set. If estop is cleared while in motion, the motor will decelerate to a stop, the
drive will turn off, and then the field will shut off.
For additional information
See the DCS800 firmware manual:
Page 148 - 152
Pages 180 – 181
Page 222
DCS800 Firmware manual supplement for North America (rev. 2.60, 2.70) Rev. b
OnOff Input (DI-7)
Off
On
On
Off
On
OnOff Input (DI-7)
On
On
On
group 10 parameters
group 21 parameters
group 44 parameters
Off2 Input*
Result
On
Field On - reduced**
On
Field On
On
Field On, then
reduced** after stop
On
Off
Field turns off safely
as motor coasts to
stop.
Off2 Input*
Result
On
Field On - reduced**
On
Field On
On
Off
Field will turn off safely
as motor coasts to stop
and cannot turn back on
again until Off2 is
switched on while
OnOff and Run are off.
Field Off
Start / Stop Select
Start / Stop
Field Excitation
5/30/2008