Electrical Connection Instructions
AC Input
AC Output
Figure 8
PD1600 series inverters are compatible with BOTH
lithium and lead acid batteries.
PD1610(1kW)
DC
WIRING
PD1618(1.8kW)
PD1620(2kW)
PD1610(1kW)
AC
PD1618(1.8kW)
WIRING
PD1620(2kW)
GND
PD1600 Series
WIRING
NOTE: To ensure optimum performance all input wires should be as short as possible. Failure to meet minimum recommended wire size will result in reduced perform-
Electrical Connection Instructions
1.
Ensure all power sources are disconnected from the inverter
2.
Remove the wiring cover
3.
Remove AC Input knockouts and AC Output knockouts
4.
Install 3/8" strain relief in AC Input and AC Output ports
5.
Connect AC Out terminal block (Ground, Neutral, and Line)
6.
Connect AC In terminal block (Ground, Neutral, and Line)
7.
Tighten strain relief (if applicable)
8.
Connect DC terminals (positive and negative) to battery with properly sized wires, 5/32" hex (PD1610); 1/4" hex (PD1618/20)
9.
When connecting DC wires a small spark may occur. This is normal charging of the inverter's internal capacitors
10. Provide external strain relief for DC wires
11. Connect equipment ground stud to a grounding point (typically the vehicle's chassis) using a 5/32" hex key
12. Re-install the wiring cover
Wiring
Positive DC
Cover
Connection
Electrical Connections Side View
ELECTRICAL CONNECTION INFORMATION
WIRE LENGTH
MIN. WIRE SIZE
0-5 ft.
#2 AWG
5-10 ft.
#1 AWG
10-15 ft.
#1/0 AWG
0-10 ft.
#2/0 AWG
0-10 ft.
#2/0 AWG
0-100 ft.
#14 AWG Solid
0-100 ft.
#14 AWG Solid
0-100 ft.
#12 AWG Solid
Any
#8 AWG
Negative DC
Equipment
Connection
Ground
Figure 9
STRIP LENGTH
Strip 3/4" (19 mm) insulation from
each cable prior to installation. Do
not leave excess copper exposed.
Strip 3/4" (19 mm) insulation from
each cable prior to installation. Do
not leave excess copper exposed.
Strip 0.6" (15 mm) insulation from
each wire prior to installation. Do not
leave excess copper exposed.
Strip 0.5" (13 mm) insulation from
each wire prior to installation. Do not
leave excess copper exposed.
WARNING: FIRE, SHOCK, AND ENERGY HAZARD
Make sure wiring is disconnected from all electrical sources before
handling. All wiring must be done in accordance with local and na-
tional electrical wiring codes.
Failure to follow these instructions may result in serious injury or
death.
AC Terminal
Blocks
DC Lugs
Ground Lug
AC Wiring
Ground Wiring
DC Wiring
Electrical Connections Top View
CONNECTION INFO
Tighten lugs to a torque of
100 in-lbs (11.3 N-m).
Do not over tighten.
Fuse: min. 100A for full load
(See NEC for safety codes)
Tighten lugs to a torque of
200 in-lbs (22.6 N-m).
Do not over tighten.
Fuse: min. 200A for full load
(See NEC for safety codes)
Standard 3/8" trade strain
relief . No torque wrench re-
quired
Torque ground lug to 30-50
in-lbs.
10