Installing the PW-6000 Input Module

Specification

Specification
The Input Board is for use in low voltage, class 2 circuits only.
Primary power
10 to 16VDC 250mA
Relay contacts
Relays 0 and 1 outputs, Form-C, 2A @ 28VDC, resistive
:
Inputs
• 16 supervised, End of Line resistors 1k ohm ± 1% tolerance
• 2 unsupervised dedicated inputs
Wire requirements
Power
RS-485
Alarm inputs
Outputs
Readers
Mechanical
Dimension
Weight
Environment
Temperature
Humidity

Set Up

Table 1: PW-6000 Input Module Jumper Settings
Jumper
J1
2
:
:
:
1 twisted pair, 18AWG
24AWG, 4,000 feet (1,200 m) max., 2-twisted pair with shield (120
23pf) (Belden 9842 or equiv.)
1 twisted pair per input, 30 ohms max.
As required for the load
6 conductors, 18AWG, 500 feet (150m) max. shield and drain
:
5.5" (140mm) W x 9" (229mm) L x 1" (25mm) H
12 oz. (340g) nominal
:
0°C to +49°C, operating, -55°C to +85°C, storage
0% to 85% RHNC
Setting
Default
OFF
X
ON
Selected
Port 1 RS-485 EOL
terminator is not active
Port 1 RS-485 EOL
terminator is active