Specification

The Output Board is for use in low voltage, class 2 circuits only.
Primary power:
12VDC + 10%, 385mA maximum
Relay contacts:
Relays 0 through 15 outputs, Form-C, 2A @ 30VDC, resistive
Inputs:
Two unsupervised dedicated inputs
Communication:
RS-485
Wire requirements:
Power
RS-485
Inputs
Outputs
Mechanical:
Dimension
Weight
Environment:
Temperature
Humidity
2
PW-7000 Output Module (PW7K1OUT) Installation Guide, Document 800-25675V1
Range 9,600 to 38,400 bps
1 twisted pair, 18AWG
24AWG, 4,000 feet (1,200 m) max., 2 twisted pair with shield
(120?, 23pF) (Belden 9842 or equiv.)
1 twisted pair per input, 30 ohms max.
As required for the load
5.5" (140 mm) W x 9" (229 mm) L x 1" (25 mm) H
12 oz. (340 g) nominal
0°C to +49°C, operating, -55°C to +85°C, storage
0% to 85% RHNC