Honeywell FF-SRS5988 Instructions For Use Manual

Dual channel emergency stop module

Advertisement

Quick Links

Dual Channel Emergency Stop Module
IMPROPER INSTALLATION
• Consult with US and/or European safety agencies
and their requirements when designing a machine
control, interface and all control elements that
affect safety.
• Strictly adhere to all installation instructions.
Failure to comply with these instructions could
result in death or serious injury.
PRODUCT DESCRIPTION
The FF-SRS5988 Emergency Stop modules are
designed to be used in emergency stop circuits
when danger to personnel or machinery is present.
This device, offering six NO and one NC closed
contact, has two internal safety relays with positive-
guided contacts to ensure redundancy.
This
safety
control
emergency stop signal to the machine control
circuitry. FF-SRS5988 helps to create a control
reliable safety solution by providing redundancy and
self-checking circuitry. Other features include high
current capability, a great number of contacts as
well as an automatic or manual start mode, cross
fault monitoring, and external relays monitoring.
APPROVALS
CE
The
product,
documentation of FF-SR Series
products carry the CE mark,
following the examination by BG
(German Berufsgenossenschaft
E+MIII). The CE declaration of
conformity
request.
cULus
This product is pending approval
(pending)
by Underwriters Laboratories Inc.
according to Canadian and U.S.
safety requirements.
FF-SRS5988
Instructions for use
module
provides
an
packaging
and
is
available
upon
(pending)
DIRECTIVES COMPLIANCE
Machine Directive 89/392 EEC
Low Voltage Directive 73/23 EEC
Electromagnetic Compatibility Directive 89/336
REGULATIONS COMPLIANCE
Regulation
Title
OSHA 29 CFR
General Requirements for
1910.212
(guarding of) All Machines
OSHA 29 CFR
(Guarding
1910.217
Power Presses
STANDARDS COMPLIANCE
Standard
Title
EN 292
Safety of Machinery - Basic
Concepts, General Principles
for Design
EN 60204-1
Safety
Electrical
Machines
EN 954-1
Safety of Machinery - Safety
related
system
ANSI B11.1
Mechanical Power Presses
ANSI B11.2
Hydraulic Power Presses
ANSI B11.19
Safeguarding
Referenced by the Other
B11 Machine Tool Safety
Standards
ANSI/RIA R15.06
Safety
Industrial Robots and Robot
Systems
UL508
Underwriters Laboratories
107018-04 EN FR26 GLO 1198 Printed in Germany
of)
Mechanical
of
Machinery
-
Equipment
of
parts
of
control
when
Requirements
for

Advertisement

Table of Contents
loading

Summary of Contents for Honeywell FF-SRS5988

  • Page 1 Electromagnetic Compatibility Directive 89/336 emergency stop signal to the machine control circuitry. FF-SRS5988 helps to create a control reliable safety solution by providing redundancy and REGULATIONS COMPLIANCE self-checking circuitry. Other features include high Regulation Title current capability, a great number of contacts as...
  • Page 2: Specifications

    SPECIFICATIONS FIG 1. CONTACT LIFE FOR Input 100% RESISTIVE LOAD (typical) Nominal voltage 120 Vac (-20%, +10%) / 24Vdc (-10%, +20%) (note 1) (Dual voltage device) 230 Vac (-20%, +10%) / 24Vdc (-10%, +20%) power factor = 1 (cos ϕ) Nominal power consumption DC: 3 W;...
  • Page 3 MECHANICAL INSTALLATION SAFETY LEVEL OF INTERFACES The FF-SRS5988 must be installed inside a The safety function of the FF-SRS5988 Safety NEMA 3 (IEC IP54) rating enclosure or better. The control module relies on dual channel safety inputs.
  • Page 4 In either mode, if the safety device is actuated Multiple wiring configurations are possible for the (emergency stop condition occurs), the normally FF-SRS5988 dual channel emergency stop module. open contact will open immediately and the normally General guidelines are provided because there are closed contacts will close.
  • Page 5 Start push- released button LED INDICATORS Input The FF-SRS5988 module has three green LED released Emergency status indicators (Power, K2 and K3) as illustrated stop activated below. The Power LED indicates power is applied to the safety control module.
  • Page 6 • If the safety device provides one safety output only (e.g., a switch driven by a direct acting mechanism like some GK, GSS, CLS or Emergency Stop push buttons), connect the FF-SRS5988 module as shown in the single input channel example To avoid any short circuit possibilities on this single input channel, use conduit to protect wiring and additional protection for the terminal strips inside the machine cabinets.
  • Page 7: Functional Description

    FIG 10. DUAL CHANNEL EMERGENCY STOP CIRCUITRY (WITH CROSS-FAULT MONITORING) Power Fuse Fuses Emergency stop Start Honeywell FF-SRS 5988 Y1 Y2 X1 X2 Machine Control This circuit has redundancy in the emergency-stop control circuit and therefore offers the highest possible safety level.
  • Page 8 L2 L3 Fuse stop Fuses Fuses Start Honeywell FF-SRS 5988 Y1 Y2 X1 X2 Machine Control This circuit has no redundancy in the emergency-stop control circuit and therefore offers a minor safety level only. CONTACT REINFORCEMENT VIA EXTERNAL CONTACTORS: With switching current >10 A, the output contacts should be reinforced by external contactors (K4 and K5)
  • Page 9: Important Notices

    SAFETY LIMIT SWITCH SEQUENCE • In order to let the module restart automatically, safety limit switch S1 must not close before switch S2. The FF-SRS5988 will only restart after the two input channels have been opened and then closed (an activation).
  • Page 10 FIG. 13. FF-SRS5988 TROUBLESHOOTING FLOW DIAGRAM (PAGE 1 OF 3) Machine Down Go to Is the "Power" LED Figure Is the power Replace the applied within safety module specifications? Apply correct voltage. 107018-04 EN FR26 GLO 1198 Printed in Germany...
  • Page 11 FIG. 14. FF-SRS5988 TROUBLESHOOTING FLOW DIAGRAM (PAGE 2 OF 3) From From Fig. 13 Fig. 15 Ensure jumper is set Manual start mode used between X1 and X2. with an external start push Ensure that Y1 and Y2 button? are closed (possible failure of optional external safety relays).
  • Page 12 FIG. 15. FF-SRS5988 TROUBLESHOOTING FLOW DIAGRAM (PAGE 3 OF 3) From Fig. 14 - Ensure jumper is set between S12/S22 Are two channel inputs - Ensure jumper is set selected? between S21/S23 - Ensure channel 1 is connected between S11/S12...