GFK-2884K
Installing an RX3i CEP001 Carrier on a DIN-rail
The carrier mounts on a standard EN 50022, 35 x 7.5 mm DIN-rail.
Conductive (unpainted) finish is required for proper grounding.
For best resistance to vibration, the DIN-rail should be installed
horizontally on a panel using screws spaced approximately 15 cm
(6") apart.
1. With a small flathead screwdriver, pull out the two DIN-rail
latches and stand the carrier on the DIN-rail.
2.
Push in the two DIN-rail latches so that the latches hold the DIN-
rail.

Panel Mounting

For applications requiring maximum or long-term resistance to mechanical vibration and shock, the panel-mounting
method is strongly recommended. A minimum panel thickness of 2.4 mm (.093") is required. The mounting diagram
below applies to both the CEP001 Carrier and CEE001 Expansion Carrier.
Note:
Tolerances on all dimensions are ±0.2 mm (0.078") non-cumulative.
Apply 1.1 to1.4 Nm (10 to12 in/lbs.) of torque to M3.5 (#6-32) steel screws threaded into tapped holes in the panel.
Figure 4: Panel Mounting
Figure 3: Installing on DIN Rail