6 Maintenance

The Phoenix Inverter does not require specific maintenance. It will suffice to check all
connections once a year. Avoid moisture and oil/soot/vapours, and keep the device
clean.

7 Error indications

With the procedures below, most errors can be quickly identified. If an error cannot be
resolved, please refer to your Victron Energy supplier.
7.1 General error indications
Problem
Inverter operation not
initiated when switched
on.
"Low battery" LED
flashes.
"Low battery" LED lights.
"Overload" LED flashes.
"Overload" LED lights.
"Temperature" LED
flashes or lights.
"Low battery" and
"overload" LEDs flash
intermittently.
"Low battery" and
"overload" LEDs flash
simultaneously.
"Low battery" and
"overload" LEDs light.
One alarm LED lights and
the second flashes.
Cause
The battery voltage is
excessively high or too low. No
voltage on DC connection.
The battery voltage is low.
The converter switches off
because the battery voltage is
too low.
The converter load is higher than
the nominal load.
The converter is switched off
due to excessively high load.
The environmental temperature
is high, or the load is too high.
Low battery voltage and
excessively high load.
Ripple voltage on the DC
connection exceeds 1,5Vrms.
The inverter is switched off due
to an excessively high ripple
voltage on the input.
The inverter is switched off due
to alarm activation by the lighted
LED. The flashing LED indicates
that the inverter was about to
switch off due to the related
alarm.
Solution
Ensure that the battery voltage is
within the correct range.
Charge the battery or check the
battery connections.
Charge the battery or check the
battery connections.
Reduce the load.
Reduce the load.
Install the converter in cool and
well-ventilated environment, or
reduce the load.
Charge the batteries, disconnect
or reduce the load, or install
higher capacity batteries. Fit
shorter and/or thicker battery
cables.
Check the battery cables and
battery connections. Check
whether battery capacity is
sufficiently high, and increase
this if necessary.
Install batteries with a larger
capacity. Fit shorter and/or
thicker battery cables, and reset
the inverter (switch off, and then
on again).
Check this table for appropriate
measures in regard to this alarm
state.