4.5 Connection of the AC cabling
This is a Safety Class I product (supplied with a protective grounding
terminal). Uninterruptible protective grounding must be provided at the
AC output terminals and/or chassis grounding point located externally
on the product. See the following instructions:
The output neutral wire must externally be bonded to the chassis This
is to ensure proper functioning of a GFCI to be installed in the AC output of
the Inverter.
- The chassis of the product must be connected to the frame (of the vehicle)
or the ground plate or hull (of a boat).
The terminal block can be found on the printed circuit board, see Appendix 0. Use a
three-wire cable with a flexible core and a cross section of 2.5 or 4 mm²
Procedure
The AC output cable can be connected directly to the terminal block "AC-out".
From left to right: "PE" (earth), "N" (neutral) and "L" (phase).
4.6 Optional Connections
A number of optional connections are possible:
4.6.1 Remote Control
The product can be operated remotely in two ways.
With an external switch.
•
With a Phoenix Inverter Control panel.
•
For connection of the switch see Appendix 0.
Observe the following when using an external switch:
Only functions if the switch on the product is switched to the "on" position.
•
Not to be connected if a remote control panel is connected.
•
For connection of the remote control panel, see Appendix 0.
Observe the following when using a remote control panel:
Only functions if the switch on the product is switched to the "on" position.
•
9