M u l ti- func tio na l Power M e ter D PM -C51 0 Ope ra tion Man ua l

5.2 Modbus Communication

5.2.1

Supported Modbus Function Codes

Function
Code
0x03
Read Holding Registers
0x06
Preset Single Registers
0x10
Preset Multiple Registers
When the protocol is Modbus RTU, the maximum address to be gathered with a single Modbus block read is 50
for function code 0x3, and the maximum address is 49 for function code 0x10. The function code 0xFE can be
used only when the protocol is Modbus RTU.
5.2.2

Modbus Communication Protocol

Modbus RTU mode is adopted with Modbus Master sending out the Request, in which the Function Code uses
0x03 to request response from Slave to correspond to values in Modbus address. In Response, Modbus Slave
responds to the values of Modbus address in the Master request. The packet format of IEEE754 is used for the
address of floating point numbers that corresponds to the register values found in table 5.2, using 2's
_5
complement packet format. The format are as follows:
The packet formats (2's complement) for the address of integers that corresponds to the register values found
in table 5.2 are shown in the example below.
5 - 6
Modbus Name
Low Word
High Byte Low Byte
Description
Read the contents of read location
Preset the contents of written location
Preset the contents of written loacations
High Word
High Byte Low Byte
Read: