Flame presence check
Check the level of the flame detection signal with the "Check
mode" function from the flame control: the LEDs from 2 to 6
indicate the flame signal level, respectively. See "LED indicator
and special function" on page 31.
Check Mode
With burner flame on:
 hold the reset button on the flame control pressed for at
least 3 sec.;
 the button colour will change from green to yellow;
 each operating status signalling LED will be compared to
20% of the maximum brightness;
 press the reset button again (<0.5sec) to reset the standard
operation of the signalling LEDs.Boiler
Clean the boiler as indicated in its accompanying instructions in
order to maintain all the original combustion characteristics in-
tact, especially the flue gas temperature and combustion cham-
ber pressure.
Gas leaks
Make sure that there are no gas leaks on the pipes between the
gas meter and the burner.
Gas filter
Replace the gas filter when it is dirty.
Combustion
If the combustion values measured before starting maintenance
do not comply with applicable legislation or do not indicate effi-
cient combustion, consult the Tab. K or contact our Technical
Support Service to implement the necessary adjustments.
It is advisable to set the burner according to the type of gas used
and following the indications in Tab. K.
7.3

Opening the burner

Disconnect the electrical supply from the burner
by means of the main system switch.
DANGER
Close the fuel interception tap.
DANGER
7.4

Closing the burner

Refit following the steps described but in reverse order; refit all
burner components as they were originally assembled.
20163413
20156526
μ A
-
+
Fig. 37
30
EN 676
CO
CO
theoretic
2
GAS
al max. 0% O
 = 1.2
2
G 20
11.7
G 25
11.5
G 30
14.0
G 31
13.7
7.2.4

Safety components

The safety components should be replaced at the end of their life
cycle indicated in the Tab. L.
The specified life cycles do not refer to the warranty terms indi-
cated in the delivery or payment conditions.
Safety component
Flame control
Flame sensor
Gas valves (solenoid)
Pressure switches
Pressure adjuster
Servomotor (electronic cam)
Oil valve (solenoid)
Oil regulator
Pipes/ oil fittings (metallic)
Flexible hoses (if present)
Fan impeller
Wait for the components in contact with heat
sources to cool down completely.
See "Access to head internal part" on page 18.
Carry out all maintenance work and mount the
casing again.
GB
Air excess
Max. output
Min. output
 1.2
 1.3
% Calibration
CO
2
= 1.3
mg/kWh mg/kWh
 100
9.7
9.0
 100
9.5
8.8
 100
11.6
10.7
 100
11.4
10.5
Life cycle
10 years or 250.000
operation cycles
10 years or 250.000
operation cycles
10 years or 250.000
operation cycles
10 years or 250.000
operation cycles
15 years
10 years or 250.000
operation cycles
10 years or 250.000
operation cycles
10 years or 250.000
operation cycles
10 years
5 years or 30.000
pressurised cycles
10 years or 500.000 start-ups
NO
X
 170
 170
 230
 230
Tab. K