5.11

Gas feeding

Explosion danger due to fuel leaks in the pres-
ence of a flammable source.
Precautions: avoid knocking, attrition, sparks and
heat.
Make sure that the fuel interception tap is closed
before performing any operation on the burner.
The fuel supply line must be installed by qualified
personnel, in compliance with current standards
and laws.
WARNING

5.11.1 Gas feeding line

Key (Fig. 20 - Fig. 21 - Fig. 22 - Fig. 23)
1
Gas input pipe
2
Manual valve
3
Vibration damping joint
4
Pressure gauge with push-button cock
5
Filter
6A Includes:
– filter
– working valve
– safety valve
– pressure adjuster
6B Includes
– working valve
– safety valve
– pressure adjuster
6C Includes
– safety valve
– working valve
6D Includes:
– safety valve
– working valve
7
Minimum gas pressure switch
8
Leak detection control, provided as an accessory or integrat-
ed, based on the gas train code. In compliance with the EN
676 standard, the leak detection control is compulsory for
burners with maximum outputs over 1200 kW.
9
Gasket, for "flanged" versions only
10 Pressure adjuster
P2 Up-line pressure of valves/adjuster
P3 Upstream pressure of the filter
L
Gas train, supplied separately
L1 The responsibility of the installer
For applications according to the Pressure Equip-
ment Directive PED 2014/68/EU, the installer is
required to provide:
suitable means for draining and venting as de-
WARNING
fined in clause K.10 of DIN EN 676;
valve proving system as defined in clause K.
14.4 of DIN EN 676.
20163413
Installation
MBC "threaded"
1
2
L1
D11854
MBC "flanged"-VGD
20065706
DMV "flanged or threaded"
20065609
CB "flanged or threaded"
20065707
20
GB
7
8
4
P 2
3
6A
P 3
L
Fig. 20
Fig. 21
Fig. 22
Fig. 23