Firing Rates; Test Boiler - Riello RS 810/M BLU Modulating Operation

Forced draught gas burner
Table of Contents

Advertisement

4.8

Firing rates

The MAXIMUM OUTPUT is chosen from within the diagram area
(Fig. 2).
The MINIMUM OUTPUT must not be lower than the minimum
limit of the diagram:
Model
RS 810/M BLU
4.9

Test boiler

The burner/boiler combination does not pose any problems if the
boiler is EC approved and its combustion chamber dimensions
are similar to those indicated in the diagram (Fig. 3).
If the burner must be combined with a boiler that has not been EC
approved and/or its combustion chamber dimensions are clearly
smaller than those indicated in the diagram, consult the manufac-
turer.
20163413
Technical description of the burner
kW
1200
Thermal power – kW
10
GB
The firing rate value (Fig. 2) has been obtained
considering an ambient temperature of 20C, an
atmospheric pressure of 1013 mbar (approx. 0 m
a.s.l.), and with the combustion head adjusted as
WARNING
shown on page 19.
The firing rates were obtained in special test boilers, according to
EN 676 regulations.
In Fig. 3 you can see the diameter and length of the test combus-
tion chamber.
Example:
Output 7000 kW - diameter 120 cm - length 6 m.
20161991
Fig. 2
D2448
Fig. 3

Advertisement

Table of Contents
loading

This manual is also suitable for:

20155875

Table of Contents