Default I/O connection diagrams

I/O connection diagram
#16 AWG BLU
#16 AWG BLU
Note: Dashed line portions indicate optional hand-off-auto switch (G302) and speed
potentiometer (G303)
X1 REFERENCE VOLTAGE AND ANALOG I/O
SHLD
#16 AWG BLU
#16 AWG BLU
NOTE: TERMINALS 40 AND 41 AVAILABLE ON R6 AND LARGER ONLY.
SIGNAL CABLE SHIELD (SCREEN)
OUTPUT FREQUENCY/SPEED REF 0-10 V, HAND
ANALOG INPUT CIRCUIT COMMON
REFERENCE VOLTAGE 10 VDC
ANALOG INPUT CIRCUIT COMMON
OUTPUT FREQUENCY 0-20mA
MOTOR CURRENT 0-20 mA
ANALOG OUTPUT CIRCUIT COMMON
AUX VOLTAGE OUTPUT +24 VDC 250 mA MAX
AUX VOLTAGE OUTPUT COMMON
DIGITAL INPUT COMMON FOR ALL
START (1) / STOP (0) - HAND
FORWARD (0) / REVERSE (1) HAND
HAND (0) / AUTO (1)
RUN ENABLE
FORWARD (0) / REVERSE (1) AUTO
STOP (0) / START (1) - AUTO
READY RUN
250VAC / 30VDC
2A
RUNNING
250VAC / 30VDC
2A
FAULT (-1)
250VAC / 30VDC
2A
EMBEDDED FIELDBUS
EFB (EIA-485)
TERMINATION SWITCH
BIAS RESISTORS SWITCH
SAFE TORQUE OFF.
FACTORY CONNECTION.
BOTH CIRCUITS MUST BE CLOSED
FOR THE DRIVE TO START.
EXTERNAL 24V AC/DC INPUT TO POWER THE
CONTROL UNIT WHEN THE MAIN SUPPLY IS
DISCONNECTED.