Power connection terminals

The following table shows the maximum wire size and required tightening torque for incoming
power, grounding and motor terminals.
Table 2. Terminal connection table
Output
Ratings
Type Code
Amps
6-Pulse; 208/240 Volt Ratings
ACQ580-0P-075A-2+C192+F289
74.8
ACQ580-0P-088A-2+C192+F289
88
ACQ580-0P-114A-2+C192+F289
114
ACQ580-0P-143A-2+C192+F289
143
ACQ580-0P-169A-2+C192+F289
169
ACQ580-0P-211A-2+C192+F289
211
ACQ580-0P-273A-2+C192+F289
248
6-Pulse; 480 Volt Ratings
ACQ580-0P-052A-4+C192+F289
52
ACQ580-0P-065A-4+C192+F289
65
ACQ580-0P-077A-4+C192+F289
77
ACQ580-0P-096A-4+C192+F289
96
ACQ580-0P-124A-4+C192+F289
124
ACQ580-0P-156A-4+C192+F289
156
ACQ580-0P-180A-4+C192+F289
180
ACQ580-0P-240A-4+C192+F289
240
ULH; 480 Volt Ratings
ACQ580-3P-052A-4+C192+F289
52
ACQ580-3P-065A-4+C192+F289
65
ACQ580-3P-077A-4+C192+F289
77
ACQ580-3P-096A-4+C192+F289
96
ACQ580-3P-124A-4+C192+F289
124
ACQ580-3P-156A-4+C192+F289
156
ACQ580-3P-180A-4+C192+F289
180

Branch circuit protection

Input power is connected to the ACQ580 irrigation drive package through a door interlocked
circuit breaker. When connected to a 240V or 480V power source, the ACQ580 with circuit breaker
is suitable for use on a circuit capable of delivering not more than 65,000 RMS symmetrical
amperes. Additional fuse protection is not required by UL when using circuit breakers as supplied.

Operation

The ACQ580 irrigation drive package uses irrigation specific software that is based on the
ACQ580 pump control firmware. The information below details items that are unique to the
ACQ580 irrigation drive package. See the ACQ580 pump control program firmware manual
(
3AXD50000035867
) for additional information on ACQ580 software and parameters.
Base
Enclosure
Input/Circuit Breaker
Drive
Designation
Frame
HP
25
R4
M3R-32W
14 AWG to 1/0 AWG
30
R5
M3R-32W
4AWG to 300 MCM
40
R5
M3R-32W
4AWG to 300 MCM
50
R6
M3R-40W
4AWG to 300 MCM
60
R7
M3R-40W
0 AWG to 500 MCM
75
R7
M3R-40W
0 AWG to 500 MCM
100
R8
M3R-40W
0 AWG to 500 MCM
40
R4
M3R-32W
14 AWG to 1/0 AWG
50
R4
M3R-32W
14 AWG to 1/0 AWG
60
R4
M3R-32W
14 AWG to 1/0 AWG
75
R5
M3R-32W
4AWG to 300 MCM
100
R6
M3R-40W
4AWG to 300 MCM
125
R7
M3R-40W
4AWG to 300 MCM
150
R7
M3R-40W
4AWG to 300 MCM
200
R8
M3R-40W
0 AWG to 500 MCM
40
R6
M3R-40W
14 AWG to 1/0 AWG
50
R6
M3R-40W
14 AWG to 1/0 AWG
60
R6
M3R-40W
14 AWG to 1/0 AWG
75
R8
M3R-40W
4AWG to 300 MCM
100
R8
M3R-40W
4AWG to 300 MCM
125
R8
M3R-40W
4AWG to 300 MCM
150
R8
M3R-40W
4AWG to 300 MCM
Terminal Wire Range & Tightening Torque
Motor Terminals
Terminals
Range
Nm
Range
2.5 Nm
10 AWG to 2/0 AWG
25 Nm
4 AWG to 300 MCM
25 Nm
4 AWG to 300 MCM
25 Nm
4 AWG to 300 MCM
31 Nm
3/0 AWG to 500 MCM
31 Nm
3/0 AWG to 500 MCM
31 Nm
2 x 1/0 AWG to 2 x 300 MCM
2.5 Nm
10 AWG to 2/0 AWG
2.5 Nm
10 AWG to 2/0 AWG
2.5 Nm
10 AWG to 2/0 AWG
25 Nm
4 AWG to 300 MCM
25 Nm
4 AWG to 300 MCM
25 Nm
4 AWG to 300 MCM
25 Nm
4 AWG to 300 MCM
31 Nm
2 x 1/0 AWG to 2 x 300 MCM
2.5 Nm
10 AWG to 2/0 AWG
2.5 Nm
10 AWG to 2/0 AWG
2.5 Nm
10 AWG to 2/0 AWG
25 Nm
4 AWG to 300 MCM
25 Nm
4 AWG to 300 MCM
25 Nm
4 AWG to 300 MCM
25 Nm
4 AWG to 300 MCM
12
Ground Lugs
Nm
Maximum
Nm
5.5 Nm
2 AWG
1.5 Nm
30 Nm
2 AWG
2.2 Nm
30 Nm
2 AWG
2.2 Nm
30 Nm
350 MCM
9.8 Nm
40 Nm
350 MCM
9.8 Nm
40 Nm
350 MCM
9.8 Nm
40 Nm
2 x 350 MCM
9.8 Nm
5.5 Nm
2 AWG
1.5 Nm
5.5 Nm
2 AWG
1.5 Nm
5.5 Nm
2 AWG
1.5 Nm
30 Nm
2 AWG
2.2 Nm
30 Nm
350 MCM
9.8 Nm
30 Nm
350 MCM
9.8 Nm
30 Nm
350 MCM
9.8 Nm
40 Nm
2 x 350 MCM
9.8 Nm
5.5 Nm
2 AWG
2.9 Nm
5.5 Nm
2 AWG
2.9 Nm
5.5 Nm
2 AWG
2.9 Nm
30 Nm
350 MCM
9.8 Nm
30 Nm
350 MCM
9.8 Nm
30 Nm
350 MCM
9.8 Nm
30 Nm
350 MCM
9.8 Nm