Set the hysteresis
The hysteresis only concerns the rising edge and the falling edge modes.
In rising edge mode, the hysteresis allows to the transmitter to stay in alarm when the measurement is between the thresh-
old and the threshold minus the hysteresis.
Ex: for a 50% RH threshold and a 10% RH hysteresis, the instrument will stay in alarm when the measurement will be between 50 and
40% RH.
In falling edge mode, the hysteresis allows to the transmitter to stay in alarm when the measurement is between the threshold and the
threshold plus the hysteresis.
Ex: for a 100% RH threshold and a 10% RH hysteresis, the instrument will stay in alarm when the measurement will be between 100
and 110% RH.
The first digit blinks, set it pressing the button briefly several times then press on the button more than 3 seconds to set the following digit..
Once the hysteresis is set, press the button more than 3 seconds to validate and set the time-delays.
Set the time-delay 1 and the time-delay 2 (600 seconds maximum)
- In rising edge mode, the time-delay 1 corresponds to the time lag before the alarm goes off when the threshold has been reached. The
time-delay 2 corresponds to the time lag before the alarm stops when the measurement is lower than the threshold minus the hysteresis.
Setting procedure: "Time 1" for the time-delay 1 is displayed then the time in second. The first digit blinks, press briefly on the button
and scroll the figures. Press on the button more than 3 seconds to validate. Repeat the process until the last digit to set the time-delay 1
value (from 0 to 600 s) and validate. "Time 2" is displayed the time in second. Repeat the process to set the time-delay 2.
- In falling edge mode, the time-delay 1 corresponds to the time lag before the alarm goes off when the threshold has been reached. The
time-delay 2, corresponds to the time lag before the alarm stops when the measurement is lower than the threshold plus the hysteresis.
The setting procedure is the same as the rising edge procedure.
- In monitoring mode, the alarm of the transmitter goes off when the measurement is below the lower threshold and higher the high
threshold. The time-delay 1 corresponds to the time lag before the alarm goes off when the measurement is below the lower threshold
and higher the high threshold. The time-delay 2 corresponds to the time lag before the alarm stops when the measurement is between the
lower and higher thresholds.
The setting procedure is the same as the rising edge procedure.
The setting of time delays is done, the measurement is displayed.
Configuration via LCC-S software (optional)
An easy and friendly configuration with the software!
It is possible to configure intermediate ranges.
To access the configuration via software:
- Set the DIP switches as shown beside.
- Connect the cable of the LCC-S to the connection of the transmitter.
Please refer to the user manual of the LCC-S to make the configuration.
The configuration of the parameters can be done either with the DIP switch or via software
(you can not combine both solutions). Switch off the sensor before settings process.
Mounting
To mount the transmitter, mount the ABS plate on the wall
(drilling: Ø 6 mm, screws and pins are supplied).
Insert the transmitter on the fixing plate (see A on the drawing
beside). Rotate the housing in clockwise direction until you hear a
"click" which confirms that the transmitter is correctly installed.
Ambient model has not any fixing plate.
4 fixing holes are inside the back housing. Use them to
install the transmitter on the required location.
Maintenance: please avoid any aggressive solvent.
Please protect the transmitter and its probes from any
cleaning product containing formalin, that may be used for
cleaning rooms or ducts.
Accessories
Please refer to the data sheet to get more information about available accessories.
1
2
3
4
S1 active switch
Precautions for use: please always use the device in
accordance with its intended use and within parameters
described in the technical features in order not to
compromise the protection ensured by the device.

Guide rapide

Français
Hygrostat
Le HST affiche en alternance la température et l'humidité, et possède un
relais programmable sur deux seuils d'humidité relative.
Symboles utilisés
Pour votre sécurité et afin d'éviter tout endommagement de l'ap-
pareil, veuillez suivre la procédure décrite dans ce document et lire
attentivement les notes précédées du symbole suivant :
Le symbole suivant sera également utilisé dans ce document.
Veuillez lire attentivement les notes d'informations indiquées après
ce symbole.
Sortie
1 relais inverseur. NO (normalement ouvert) : 5 A/NC (normalement fermé) : 3 A/240 Vac. Tension de mode commun < 30 Vac
Alimentation
Consommation
État du relais / Alarme
Directives européennes
2014/30/UE CEM ; 2014/35/UE Basse Tension ; 2011/65/UE RoHS II ; 2012/19/UE DEEE
Raccordement électrique
Communication PC
Environnement
Connectiques
Intérieur de la coque avant
1
2
1. Switch inactif
2. Switch actif (S1)
Inside the front housing
3. Connexion LCC-S
4. LED Alarme
Raccordements électriques suivant normes NFC15-100
Seul un technicien formé et qualifié peut
réaliser cette opération. Pour réaliser
le raccordement, l'appareil doit être
1
2
HORS-TENSION.
NO : normalement ouvert
COM : commun
NC : normalement fermé
24 Vac/Vdc ±10 %
3 VA
LED rouge en façade et buzzer interne (70 dB à 10 cm)
Bornier à vis pour câbles Ø 0.05 à 2.5 mm
2
. Réalisé suivant les règles de l'art
Câble USB-mini Din
Air et gaz neutre
Boîtier arrière xe
Face avant mobile
6
4
3
5
8
5. Bouton pour réglages
6. Bornier relais
Fixed back housing
7. Bornier alimentation
Removable front face
8. Presse-étoupes
6
NO COM NC
1
2
3
4
5
6
7
4
3
5
8
-
+
Alimentation
ou
24 Vdc
6
NO COM NC
7
7
6
7
~
~
N
L
N
L
~
~
Alimentation
24 Vac
Classe II
7