Delta RPI-M8 Manual page 54

Hide thumbs Also See for RPI-M8:
Table of Contents

Advertisement

1. Insufficient input power
HW DSP
2. Auxiliary power circuitry
ADC3
malfunction
3. Detection circuit malfunction
1. Insufficient input power
HW Red
2. Auxiliary power circuitry
malfunction
ADC1
3. Detection circuit malfunction
1. Insufficient input power
HW Red
2. Auxiliary power circuitry
malfunction
ADC2
3. Detection circuit malfunction
1. The calibration is incorrect
HW
2. Current feedback circuit is
Efficiency
defective
1. Red. CPU is idling
2. The communication
HW COMM2
connection is disconnected
1. DSP is idling
2. The communication
HW COMM1
connection is disconnected
3. The communication circuit
malfunction
1. PV array insulation fault
2. Large PV array capacitance
between Plus to Ground or
Ground
Minus to Ground
Current
3. Either side of boost driver or
boost choke malfunction
4. Detection circuit malfunction
1. Power line is disconnected
HW Connect
inside the inverter
2. Current feedback circuit is
Fail
defective
1. RCMU is disconnected
RCMU Fail
2. Detection circuit malfunction
1. Check the input voltage, must > 150Vdc
2. Check the auxiliary circuitry inside the inverter
3. Check the detection circuit inside the inverter
1. Check the input voltage, must > 150Vdc
2. Check the auxiliary circuitry inside the inverter
3. Check the detection circuit inside the inverter
1. Check the input voltage, must > 150Vdc
2. Check the auxiliary circuitry inside the inverter
3. Check the detection circuit inside the inverter
1. Check the accuracy of current and power
2. Check the current feedback circuit inside the
inverter
1. Check reset and crystal in Red. CPU
2. Check the connection between Red. CPU and
DSp
1. Check reset and crystal in DSP
2. Check the connection between DSP and
COMM
3. Check the communication circuit
1. Check the insulation of Solar inputs
2. Check the capacitance (+ <-> GND & - <->
GND), must < 2.5uF. Install a external
transformer if necessary
3. Check boost driver & boost choke
4. Check the detection circuit inside the inverter
1. Check the power lines inside the inverter
2. Check the current feedback circuit inside the
inverter
1. Check the RCMU connection inside the
inverter
2. Check the detection circuit inside the inverter
53