Technical Data - Bosch ACC MT Installation Instructions Manual

Central controller with touch display air center control
Hide thumbs Also See for ACC MT:
Table of Contents

Advertisement

2.7

Technical data

The PoE+ (Power over Ethernet) function is not available for
devices with the part number 8733502082.
Device designation
Construction
Weight
Dimensions
Power supply
Electricity consumption
Display
Connections, basic device
Connections for expansion card
Protection index
Ambient conditions, operation
Ambient conditions, transport
Ambient conditions, storage
SELV voltage
Rated impulse voltage
Operating principle according to IEC/EN 60730-1
Software class according to IEC/EN 60730-1
Specified voltage and specified current for the purpose of EMC
interference tests
Table 3
Technical data
Air Center Control – 6720892132 (2021/10)
Air Center Control ACC MT
Electronic, separately installed controller for surface installation
1590 g
1820 g (Part number 8733502082)
271 × 188 × 42 mm
24 V DC 1A or PoE+ and 24 W (802.3at)
Max. 24 W, typical 10.2 W
10.1" WXGA (1200 × 800) with PCAP-Touch
USB (Type A, max. 500 mA, max. 32 GB, FAT 32)
LAN (100 Mbit/s)
1 × XYE
2 × Digital In (24 V DC, max. 15 mA)
2 × Digital Out (Dry-Contact, max. 24 V AC/DC, continuously
max. 250 mA (max. 2 A peak))
1 × micro SD card
1 × LAN (100 Mbit/s)
3 × XYE
1 × ModBus/RTU (max. 115 kbit/s)
1 × Analogue In (0...10 V)
1 × Analogue Out (0/4...20 mA)
IP30
0...40 °C, 5...85 % RH, pollution degree 2
–30...70 °C, 5...95 % RH
–25...55 °C, 5...95 % RH
Max. 57 V DC
DC
, PoE+:1500 V; other connections: 500 V
in
Type 1
A
24 V/0,7 A