Hitachi PSC-A32MN Installation And Operation Manual page 81

Central station
Hide thumbs Also See for PSC-A32MN:
Table of Contents

Advertisement

Operation
Outdoor unit capacity control
5 Select the value for Outdoor Unit Capacity.
The selected capacity value button is highlighted in yellow.
6 Use the buttons on the right side of the screen in order to schedule outdoor unit capacity control when there is no external input
contact being applied for this purpose.
Select "Enable" or "Disable".
Tap " " or " " to set the applicable starting time and ending time, in 30 minute steps.
When the ending time falls earlier than the starting time, ending time becomes effective on the next day.
For example :
Ending Time 08:00,
7 Tap "Register"
8 Select the target of capacity control (Refrigerant system).
The buttons of the numbers of refrigerant systems of registered outdoor units are indicated in blue.
The buttons of the numbers of refrigerant systems of unregistered outdoor units are indicated in grey. These refrigerant systems
cannot be selected.
Tap the button of a refrigerant system number in order to switch its selection state.
Tap "Selec.all refr.syst" to switch the selection state of all refrigerant systems.
The selected refrigerant systems are indicated with a check mark.
9
73
PMML0332A rev.0 - 05/2015
(8)
(6)
(7)
(9)