Step 3: Install the UC400 2H/2C and Air-Fi® Wireless for Non-Trane
RTUs
If required for this site, install the UC400 2H/2C and Air-Fi® Wireless on non-Trane equipment. For
more information, see Tracer UC400 Pre-programmed for RTU or Heat Pump (X39641251-01B). The
point list below is for your convenience.
Table 2.
Inputs and Outputs
Note: Ensure Air-Fi® Wireless and zone sensors are addressed per the submittal.
BAS-SVN040B-EN
Tracer® UC400 2H/2C RTU controller inputs and outputs
Label
AI1
AI2
AI3
Analog Inputs
AI4
AI5
P1
P2
UI1
Universal Inputs
UI2
BI1
BI2
Binary Inputs
BI3
BI4
BI5
AO1
Analog Outputs
AO2
BO1
BO2
BO3
BO4
Binary Outputs
BO5
BO6
BO7
BO8
BO9
Functions
Space Temperature Sensor
Space Temperature Setpoint
--
Discharge Air Temperature Sensor
Outdoor Air Temperature Sensor
--
--
--
Occupancy Input (Binary)
Condensate Overflow Input
Heat Pump Selection Input
Supply Fan Status
--
--
--
--
Supply Fan Start Stop Command
--
--
Compressor 1 Command
Compressor 2 Command
Heat Stage W1 Command
Heat Stage W2 Command
Reversing Valve Command
Auxiliary Heat Command
Installation
Descriptions
10kΩ Thermistor
1kΩ Input
10kΩ Thermistor
10kΩ Thermistor
--
--
--
Open = Occupied, Closed = Unoccupied
Open = Normal, Closed = Alarm
Open = DX, Closed = Heat Pump
Open = Off, Closed = On
--
--
--
--
--
--
--
--
--
--
--
Off = Cooling, On = Heating
--