Use Copper Conductors Only!
Failure to use copper conductors could result in equipment damage as the equipment was not
designed or qualified to accept other types of conductors.
To ensure proper operation of the controllers, install the power supply circuit in accordance with
the following guidelines:
Note: The transformer voltage utilization range is 98–132 Vac (120 Vac nominal).
1. Lock open the supply-power disconnect switch.
2. At the top-right corner of the enclosure, remove the knockout for 0.50 inch (13 mm) conduit.
3. Open or remove the enclosure door if it is already installed.
4. Inside of the enclosure at the top-right corner, remove the line voltage area cover plate.
5. Feed the 120 Vac power wire into the enclosure.
6. Using
7. Connect the neutral wire to the 'N' terminal.
8. Connect the green ground wire to the chassis ground screw.
Note: The ground wire should be continuous back to the circuit breaker panel.
Hazardous Voltage!
Failure to follow instructions below could result in death or serious injury. Alwaysmake sure to
put the cover plate back in place before operating the controller.
9. Replace the cover plate.
10. On a field-supplied label, record the location of the circuit breaker panel and the electrical
BAS-SVN040B-EN
The panel must receive power from a dedicated power circuit. Failure to comply could cause
panel malfunctions.
A disconnect switch for the dedicated power circuit must be near the panel, within easy reach
of the operator, and marked as the disconnecting device for the panel.
Do not run input or output wires in the same conduit or wire bundle with high voltage wire or
24 Vac wiring. Failure to comply could cause the controller to malfunction due to electrical
noise.
Power wiring must comply with the National Electrical Code™ (NEC) and applicable electrical
codes.
120 Vac wiring requires three-wire service (Line, Neutral, Ground). Refer to Panel 10 for terminal
locations.
Figure 8, p.
14, connect the line wire to the 'L' terminal.
circuit. Attach the label to the cover plate.