Type &
Object name
Instance
On-Off Control
BV 5
Temperature Scale BV 6
Relay 1 Control
BV7
Relay 2 Control
BV8
Relay 3 Control
BV9
Relay 4 Control
BV10
Relay 5 Control
BV11
Relay 6 Control
BV12
Relay 7 Control
BV13
Occupancy
BV 14
Command
Fan Output
BV15
for Heating
Sensor type
BV16
MSV 0
Fan Mode
System Mode
Sleep
MSV3
Temperature
Source
Lowest Fan
Speed
Fan Speed Status
UM-15090500-AA1
Readable/
Writable
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
MSV 1
R/W
MSV 2
R/W
R/W
MSV 4
R/W
MSV 5
R
Description
On/Off Status of Thermostat 0: Off, 1: On
°C/ °F
On/Off Control of Relay 1
(Cooling Stage 1)
On/Off Control of Relay 2
(Cooling Stage 2)
On/Off Control of Relay 3
(Heating Stage 1)
On/Off Control of Relay 4
(Heating Stage 2)
On/Off Control of Relay 5
On/Off Control of Relay 6
On/Off Control of Relay 7
Fan
Room Occupancy Setting
Disable/ Enable Fan
Output for Heating
Select Sensor type
Fan Mode
Working Mode: Heat, Cool or
Ventilation
Sleep (Only for Models with
Sleep Function Available).
Current Temperature Source
Lowest Fan speed in
Auto Fan mode
Fan Speed Status
Range and Definition
0: °C
1: °F
0: Off, 1: On
0: Off, 1: On
0: Off, 1: On
0: Off, 1: On
0: Off, 1: On
0: Off, 1: On
0: Off, 1: On
0: Occupied,
1: Unoccupied
0: Disable
1: Enable
0: CO2
1: RH
1: Auto 1: Low
3: Med.4: Hi
1: Cool Mode
2: Heat Mode
3: Ventilation @ Cool Mode
4: Ventilation @ Heat Mode
1: Disable,
2: 0 Hr. Sleep
3: 0.5 Hr. Sleep
4: 1 Hr. Sleep
5: 1.5 Hrs. Sleep,
6: 2 Hrs. Sleep
1: Built-In Temp. Sensor
2: Remote Temp. Sensor
3: Assigned through BACnet
1: Stop 2: Low
3: Med. 4: Hi
1: Stop 2: Low
3: Med
4: Hi