Type &
Object name
Instance
Current Dew Point
AI 5
Current CO
2
AI 6
Reading
Control Valve
AI 7
Feedback
Modulating/
AI 8
Floating Output 1
Modulating/
AI 9
Floating Output 2
Modulating Fan
AI 10
Output
CO2 Control Output
AI 11
Percentage
Voltage Input Value
AI 12
AI 1
AI 13
Percentage
AI 2
AI 14
Percentage
AI 3
AI 15
Percentage
Cooling Temperature
AV 0
Setpoint
Space
AV 1
Temperature
Via BACnet
Timer Off
AV 2
Heating Temperature
AV 3
Setpoint
Hr-Running Time
AV 4
M-Running Time
AV 5
Sec-Running
AV 6
Time
AV 7
Deadband
Unoccupied Cool
AV 8
Setpoint
Unoccupied Heat
AV 9
Setpoint
UM-15090500-AA1
Readable/
Description
Writable
Current Dew Point (221CH
R
models only)
Current CO
R
Control Valve Feedback
R
Modulating/ Floating Output
R
1
Modulating/ Floating Output
R
2
Modulating Fan Output
R
CO2 Control Output
R
Percentage
Voltage Input Value
R
Analog Input 1 Percentage
R
Value
Analog Input 2 Percentage
R
Value
Analog Input 3 Percentage
R
Value
Cooling Temperature Set
R/W
Point
BACnet
R/W
Assigned Current
Temperature
Timer Off (Only for Models
with Countdown Timer
Function
R/W
Available).
Heating Temperature Set
R/W
Point
Running Time of Valve (Hr.)
R/W
Running Time of Valve
(M.)
R/W
Running Time of Valve
(Sec.)
R/W
R/W
Deadband
Unoccupied Cooling Setpoint
R/W
Unoccupied Heating
R/W
Setpoint
Range and Definition
-999~9999: -99.9~999.9
°C/°F
Reading
0~3000: 0~3000 ppm
2
0~1000 (0.0%~100.0%)
0~100: 0~100 %
0~100: 0~100 %
0~100: 0~100 %
0~100: 0~100 %
0~150 (0.0~15.0 VDC)
0~1000 (0.0%~100.0%)
0~1000 (0.0%~100.0%)
0~1000 (0.0%~100.0%)
°C :0~500 (0.0~50.0℃)
°F: 320~1220
(32.0~122.0°F)
-999~9999
(-99.9~999.9℃/°F)
0~24: 0~24 Hours Count
Down
0: Disable
℃/°F
-999~9999: -99.9~999.9
0~65535 (Hr.) For
Reading But 0~30000 (Hr.)
For Writing.
0~59 (Minute)
0~59 (Sec.)
°C: 0~100 (0.0~10.0 °C)
°F: 0~180 (00~18.0 °F)
°C: 250~300 (25.0~30.0°C)
°F: 770~860 (77.0~86.0°F)
°C: 100~220 (10.0~22.0°C)
°F: 500~715(50.0~71.5°F)