Error Code Table - ECR International Dunkirk DCBF-125 Installation, Operation And Maintenance Manual

Condensing gas fired boiler
Hide thumbs Also See for Dunkirk DCBF-125:
Table of Contents

Advertisement

NOTE: When instructed press and hold
the 'Reset' for between 1-3 seconds to
reset the boiler.
Table Of Error Codes
Gas valve connection cable
m ag
m 10
External probe fault
m 12
Water flow switch open
m 13
Water flow switch close
m 15
gas valve fault
m 18
Water refill enabled
m 19
Max lime of water refill
Central Heating Flow NTC Fault
m 20
Flue NTC Fault
;20
! 4 0
Central Heating Return NTC Fault
m 5 o
Hot Water NTC Fault (tank version)
;53
Obstruction on the flue pipe- combustion off
PCB to be set by the "Calibration Function"
m 55
m
Fan parameler Out of range in autocalibralion
71
Combustion test Out of range in autocalibration
m72
mn
Current out of range
Minimum gas valve current
!;78
m
Maximunm gas valve current
79
Communication error
!;83-87
Combustion test alarm during auto-setting
!;92
m
109
Pre-Circulation Fault
m 110
Safety Thermostat Operated
m
117
System Water Pressure Too High
m11s
System Water Pressure Too Low
m
125
Circulation Faull (Primary Circuit)
m
120
Flame Failure
m
129
Frequently loss of flame during the ignition
m 130
Flue NTC Operated
m
Interruption Of Gas Supply or Flame Failure
133
m
Elapsed time Gas valve open without gas
13 4
m 135
Interruption Of Gas Supply (internal error)
m
Fan or Fan Wiring Fault
1s o
!;321
Domestic Hot Water NTC sensor fault
;38 4
False flame
;385
Under voltage

ERROR CODE TABLE

Initial Fault Finding Checks
1. Check that gas, water and electrical supplies are available
at the boiler.
2. Electrical supply= 120V -60 Hz.
3. The preferred minimum gas pressure is 3.5"wc for
Natural gas and 10"wc for LPG.
4.
Carry out electrical system checks, i.e. Ground
Continuity, Resistance to Ground, Short Circuit and Polarity
wilh " a suitable meter.
NOTE: These checks must be repeated after any servicing
or fault finding.
5. Ensure all external controls are calling for heat and check
all external and internal fuses. Before any servicing or
replacement of parts, ensure th� gas and electrical supplies
are isolated.
1. If a fault occurs on the boiler an error code may be shown
by the facia display.
!;20, fs28, !;40, !;5o, 1!1 1 60, 1!1321 and 1!1 4 31 indicate possible
faulty components.
l!l 53 shows possible obstruction in the flue duct.
I; 55 indicates that the pcb is not setting/calibrated.
1!71, 1!72, �7,
new calibration is needed.
1!192 shows possible flue recirculation in the flue duct.
I; 83 ... 87 shows possible error of communication with
thermostat (Goto section P)
!;110 shows overheat of the primary.
1!1117 is displayed when the primary water pressure is more than
43 psi.
!;118 is displayed when the primary water pressure is less
than 7.25psi.
!;125 is displayed in either of two situations:-
0 If within a time between 15 .. 30 seconds of the burner lighting
the boiler temperature has not changed by 2 •F.
ii) If within 10 minutes of the burner lighting the boiler
temperature twice exceeds the selected temperature by 80
these instances poor primary circulation is indicated.
!;128 is displayed if there has been a flame failure during normal
burner operation.
I; 133 , I; 134 and I; 135 indicate that the gas supply has been
interrupted, ignition has failed or the flame has not been
detected.
2. By pressing the 'Reset' button for between 1-3 seconds when
ti
110,l!I 125, l!I 133,
are displayed it is possible to relight the boiler.
3. If this does not have any effect, or error codes are displayed
regularly further investigation is required.
37
!;?a
e tl2 indicate possible wrong calibration. A
m
134,I; 135 ,'3 09, '3 1s,'3128 andl3384
PN 240012875 REV. A [01/31/2020]