Application Table - Indirect Tank Sizing - ECR International Dunkirk DCBF-125 Installation, Operation And Maintenance Manual

Condensing gas fired boiler
Hide thumbs Also See for Dunkirk DCBF-125:
Table of Contents

Advertisement

APPLICATION TABLE - INDIRECT TANK SIZING

'HEATING ONLY' BOILER (125,000 BTUH)
H2O30
1st HOUR RATING
(GAL/HR)
CONTINUOUS
RATING (GAL/HR)
H2O40 / H2O40L
1st HOUR RATING
(GAL/HR)
CONTINUOUS
RATING (GAL/HR)
H2O50
1st HOUR RATING
(GAL/HR)
CONTINUOUS
RATING (GAL/HR)
H2O60 / H2O60L
1st HOUR RATING
(GAL/HR)
CONTINUOUS
RATING (GAL/HR)
Notes:
176 °F Boiler Supply Water Temperature
AHRI Rating Conditions - 50 °F Inlet Water
@ 4.0 GPM FLOW RATE
Boiler output over 100,000 BTU does not effect
tank performance.
BOILER OUTPUT (BTUH/HR)
50,000
140 F
94
115 F
119
140 F
67
115 F
92
140 F
103
115 F
128
140 F
67
115 F
92
140 F
112
115 F
137
140 F
67
115 F
92
140 F
121
115 F
146
140 F
67
115 F
92
33
60,000
80,000
106
106
138
158
79
79
111
131
115
119
147
174
79
83
111
138
124
133
156
192
79
88
111
147
133
147
165
208
79
93
111
154
PN 240012875 REV. A [01/31/2020]
100,000
106
158
79
131
119
174
83
138
133
192
88
147
147
208
93
154