• Care should be taken to separate high voltage power from low voltage (Class 2) control wiring.
• All connections to sensor are low voltage, Class 2.
Standard wiring with two local off switches
Neutral
White
BZ-200
Hot
Black
Power Pack
**Ground
** BZ-200 Power Pack
must be grounded to
ensure signal integrity,
not for safety ground.
Directly to Ceiling
1. Attach the plastic spring clips to the edge of the sensor in the slots provided.
2. Cut a 3.5" to 4" round hole in the acoustic ceiling tile at the mounting location. A 3.5"
hole is recommended for a secure fit.
3. Pull the low voltage wire from the power pack to the sensor through the hole.
4. Connect the low voltage wires to the appropriate terminals on the sensor.
5. Push the sensor up through the hole until the Spring Clips hold the sensor securely
in place.
6. Snap the front cover onto the sensor.
Using an Octagonal J-Box
1. Pull the low voltage wires from the power pack into the J-Box through the conduit
knockout.
2. Connect the low voltage wires to the appropriate terminals on the sensor.
3. Loosen the appliance mounting screws attached to the J-Box.
4. Align the sensor in the J-Box so that the mounting screws on the box match the key
holes on the sensor's rear housing.
5. Push the sensor up into the J -Box and twist it so that the mounting screws are seated
in the keyhole slots.
6. Tighten the two screws to secure the sensor to the J-Box.
7. Snap the front cover onto the sensor.

CONNECTING WIRES

Optional
Local Off
Switch
Fixture
Optional
Local Off
Switch
Red
Red
Fixture
Low Voltage Wires
Control Output
DT-300/DT-305
Low Voltage
Common
Occupancy
+24VDC
Sensor

MOUNTING THE SENSOR

Manual-On wiring with low voltage momentary switch
White
Neutral
Hot
Black
**Ground
Cap
Cap
** BZ-250 Power Pack
must be grounded to
*To
Additional
ensure signal integrity,
not for safety ground.
Sensor(s)
3
Red
BZ-250
Auto
Man
ON
ON
Red
Power Pack
(A)
Low Voltage
LVSW-101
Wires
Low Voltage
Switch Input
Control Output
DT-300/DT-305
Low Voltage
Common
Occupancy
+24VDC
Sensor
Ceiling Mount
J-Box Mount
Fixture A
SW1
COM
*To
Additional
Sensor(s)