Backup Batteries - Honeywell SILENT KNIGHT SK-5208 Installation And Operation Manual

Fire control/communicator
Table of Contents

Advertisement

Model SK-5208 Fire Control/Communicator Installation and Operation Manual
3.8

Backup Batteries

The control panel battery charge capacity is 7.0 to 35.0 AH. Use 12V batteries of the same AH
rating. Determine the correct AH rating as per your current load calculation (see 3.6.2).
Wire batteries in series to produce a 24-volt equivalent. Do not parallel batteries to increase
the AH rating.
Batteries larger than 18 AH (not to exceed 35 AH) use the RBB Remote Battery Box. It is
recommended that you replace the batteries every five years. The following steps and diagram
explain how to connect the batteries.
1. Connect the black wire to the negative (-) side of battery #1.
2. Connect the jumper wire provided (P/N 140694) from the positive (+) side of battery #1 to
the negative side of battery #2.
3. Connect the red wire to the positive (+) side of battery #2
Control Panel
Note: Replace batteries
every 5 years.
Apply AC power before connecting the batteries to the power supply to prevent arcing on battery terminals.
Note: The total current draw on smoke power, accessory power, and notification device outputs must not exceed
6A.
3-10
RED
Black
Battery Jumper
Shipped With Panel
Battery #1
UL Listed 12VDC Battery
Gell Cell
Caution
firealarmresources.com
(P/N 140694)
Battery #2
UL Listed 12VDC Battery
Gell Cell
P/N 151204