Honeywell SILENT KNIGHT SK-5208 Installation And Operation Manual page 78

Fire control/communicator
Table of Contents

Advertisement

Model SK-5208 Fire Control/Communicator Installation and Operation Manual
Programming
Menu Item
Option
Silence Relay
Fire Relay
Prealarm Relay
Aux Relay
Waterflow Relay
Superv Relay
Relay Options
Crossalert A Relay _ _ _ _
Release A Relay
Crossalert B Relay _ _ _ _
Release B Relay
Trouble Relay
Fire Drill Relay
AC Trbl
Code # Type
User (1-10) #
Code
User # Code
4-20
Table 4-4: Programming Options
Choices
Default
No Relays
_ _ _ _
selected
Relay 1
1 _ _ _
selected
No Relays
_ _ _ _
selected
No Relays
_ _ _ _
selected
No Relays
_ _ _ _
selected
No Relays
_ _ _ _
selected
No Relays
selected
No Relays
_ _ _ _
selected
No Relays
selected
No Relays
_ _ _ _
selected
_ _ _ 4
4
Relay 1
1 _ _ _
selected
No Relays
_ _ _ _
selected
5208 and
Installers
123456
Operators
1111
Not Used
Enter 3 to 6 digit
number
firealarmresources.com
Comments
If a relay is selected, that relay can be silenced for
Trouble and Supervisory conditions only. (This
includes relays programmed for AC Trbl.)
If a relay is selected, that relay will activate for fire
alarm conditions.
If a relay is selected, that relay will activate for
prealarm conditions.
If a relay is selected, that relay will activate for
Auxiliary conditions.
If a relay is selected, that relay will activate for
waterflow conditions.
If a relay is selected, that relay will activate for
supervisory conditions.
If a relay is selected, that relay will activate for
crossalarm conditions.
If selected will activate for releasing group "A".
If a relay is selected, that relay will activate for
crossalarm conditions.
If selected will activate for releasing group "B".
Relay will be activated when no troubles exist and
will deactivate when a trouble condition occurs.
If a relay is selected, that relay will activate for fire
drills.
If a relay is selected, that relay will be activated
when AC is normal and will deactivate when a
Low AC condition exists.
Enter any value from 001 to 999999.
P/N 151204

Advertisement

Table of Contents
loading

Table of Contents