Section 6

Reporting

The SK-5208 can transmit information in four different formats. This section describes the
four basic reporting formats of the SK-5208 and the codes that they send to a central station
receiver. Of these four formats some of the formats offer a more specific selection for that
format. For example, you can select a 3/1 format that requires a 1400 or 2300 Hz handshake,
or SIA format that can handle 8 or 20 events per call. Selecting the correct format depends on
the type of receiver that will receive calls from the SK-5208.
The SK-5208 DACT is compatible with Silent Knight Model 9800 and 9500 Digital
Receivers.
6.1

Reporting Formats

This section gives a description of each of the SK-5208 reporting formats. Refer to Table 6-1.
Format Name
Category
Programming
Name
3/1 14
3/1
3/1 23
4/2
SK4/2 1400
SIA8
SIA
SIA20
Contact ID
Contact ID
P/N 151204
Table 6-1: Reporting Formats Descriptions
Name
Old format, transmits a 3-digit account number and a 1-digit event
code. Transmissions are acknowledged at 1400 Hz.
Old format, transmits a 3-digit account number and a 1-digit event
code. Transmissions are acknowledged at 2300 Hz.
Tone burst format, transmits a 4-digit account code and 2-digit
event code. Transmissions are acknowledged at 1400 Hz.
Security Industry Association standard communication format
which send a maximum of 8 events per call.
Security Industry Association standard communication format
which send a maximum of 20 events per call. Up to a 6-digit
account number.
Ademco Contact ID format. DTMF (Dual Tone Multiple
Frequency) format. Send a 4-digit account number. Transmission is
acknowledged at both 1400 and 2300 Hz.