Standby Battery Current
Convert the total from Table 1
to amps and enter here
Notes:
Batteries available from FireLite
Technical Manuals Online! - http://www.tech-man.com
Table 2: Power Supply Loading
Basic Control Panel (all zones in alarm)
If using the Zone Relay Module, add
64 mA for the MS-4012 or 32 mA for the MS-4024
If using General Alarm & Trouble Module: add
18 mA for the MS-4012 or 10 mA for the MS-4024
If using the Transmitter Module (40xxTM), add 13 mA
If using the Reverse Polarity Trouble output, add 10 mA
Current (in mA) drawn from Non-resettable Power (TB3)
Place subtotal from line d, Table 1 here
Add column for Total Alarm Current:
(Total Alarm Current cannot exceed 550 mA)
Table 3: Ampere-Hour Calculations
amps
X
Enter 0.3 for 5 minutes in alarm
or 0.6 for 10 minutes in alarm +
Add Standby and Alarm amp/hours
Select a battery with a greater amp/hour rating.
* NFPA 72 Local and 72 Proprietary Protected Premises systems require 24 hours of standby.
* NFPA 72 Auxiliary and 72 Remote Station systems require 60 hours of standby.
* The battery charger in this panel will charge a maximum of 9 AH batteries within 48 hours (6 AH minimum).
(Batteries larger than 7-AH battery will have to be mounted in a separate cabinet adjacent to panel).
PS-1242 4.2 AH @ 12 VDC (MS-4012 requires two)
PS-1270 7.0 AH @ 12 VDC (MS-4024 requires two)
firealarmresources.com
Standby Time
24 or 60 hours
hours
=
=
15586 Rev E
5/14/93
P/N 15586:E
340 mA
340 mA
340 mA
340 mA
340 mA
Standby
amp/hours
Alarm
amp/hours
Total amp/hours
needed