A.6 Zone Relay Module (40xxZR)
Contacts rated for:
Note: For U.L.C. applications, contacts are derated for: 2.0 amps @ 30 VDC (resistive)
A.7 General Alarm and Trouble Relay Module (40xxAT).
Contacts rated for:
Note: For U.L.C. applications, contacts are derated for: 2.0 amps @ 30 VDC (resistive)
A.8 Four-wire Smoke Detector Power
Up to 200mA of current can be provided to four-wire smoke detectors. Note: If using Non-Resettable
power (Terminal Block 3), the combined current shall be limited to 50 mA.
A.9 Unregulated, Unfiltered Power
Total DC current available for powering external devices is 1.0 amp (subtracted from indicating appliance
power).
A.10 Non-resettable Power
DC current available from this output and four-wire smoke power output combined is 50mA.
A.11 Cabinet Dimensions
Technical Manuals Online! - http://www.tech-man.com
2.0 amps @ 30 VDC (resistive) 0.5 amps @ 120 VAC (resistive)
2.0 amps @ 30 VDC (resistive) 0.5 amps @ 120 VAC (resistive)
Door = 15-1/4"
Backbox = 15"
15586 Rev E
firealarmresources.com
0.5 amps @ 30 VAC (resistive)
0.5 amps @ 30 VAC (resistive)
Door = 14-3/4"
Backbox = 14-1/2"
5/14/93
P/N 15586:E
Cabinet = 2-7/8"
Backbox = 2-1/2"