Cooling - Trane VLT AQUA Drive FC 202 VLT AutomationDrive FC 301 Instruction Manual

Vertical bypass/non bypass panel
Table of Contents

Advertisement

Installation

3.3 Cooling

Only mount the drive and panel vertically.
Panels rely on the ambient air for cooling. It is
important to observe the limitations on ambient
3
3
air temperature. The maximum ambient
temperature for all bypass panels is 40°C and
45°C for non bypass panels. Derating concerns
start above 3300 feet elevation above sea level.
Most panels may be mounted side-by-side
without additional side clearance. However, the
P2 (B3 frame size) units require 1.5 in. minimum
clearance between units (see Figure 3.2).
Top and bottom clearance is required for cooling
(see Figure 3.3). Generally, 2 to 10 inches (50 to
250mm) minimum clearance is required,
depending upon the hp (kW) of the unit. See the
dimensional drawings in 8 Appendix for specific
requirements.
No additional back plate is required for drives
with the bypass and non bypass panels.
Figure 3.2 Side Cooling Clearance
3-6
Vertical Bypass/Non Bypass Panel
38.1 [1.5]
®
MG.13.A1.22 - VLT
is a registered Danfoss trademark
AIRFLOW
50.8 [2.0] min
101.6 [4.0] min
AIRFLOW
Figure 3.3 Cooling Airflow
CEILING
FLOOR