Installing the PRO3200 Output
Module

Description

The Output Board provides connections for 16 relay outputs. You can either mount the
board in a rack or open and flat. If you rack-mount the board, only one edge is
accessible for wiring; however, a flat mount increases the amount of available I/O
slightly but significantly decreases the number of boards that can be mounted in one
enclosure.
Starting at the bottom of the rack-mount side of the board:
• The first connector provides power to the board.
• The next connector provides communication with the Controller (PRO22IC or
• Continuing up this edge, the next six connectors provide 12 relay output
When the board is mounted flat, four additional relay outputs and two dedicated inputs
for cabinet tamper and power fault detection are provided on the opposite edge of the
board.
All 16 form-C relay outputs are designed to handle dry-circuit signals. The two
dedicated inputs are non-supervised. Communication to the control panel is
accomplished via an RS-485 interface. This board requires 12 VDC input power.
When communication to the controller is lost, this board maintains all previous output
settings at the time communication was lost.

Specification

The Output Board is for use in low voltage, class 2 circuits only.
Primary power
10 to 14VDC 385mA maximum
12VDC @ 200mA nominal
Relay contacts
Relays 0 through 15 outputs, Form-C, 2A @ 28VDC, resistive
:
Inputs
Two unsupervised dedicated inputs
Communication
RS-485
PRO3200 Output Module Installation Guide, Document 800-15465
PRO32IC).
connections.
:
:
:
Range 9,600 to 38,400 bps